SPARC S7-2 Server Service Manual

Exit Print View

Updated: March 2017
 
 

Install a Fan Module

This is a hot-service procedure that can be performed by a customer while the server is running.

  1. Remove the replacement fan module from its packaging and place it on an antistatic mat.
  2. With the fan door open, position the replacement fan module into the server.

    The fan modules are keyed to ensure that they are installed correctly.


    image:Graphic showing fan module installation.
  3. Press down on the fan module and apply firm pressure to fully seat the fan module.
  4. Verify that the fan module status indicator (LED) that aligns with the replaced fan module is extinguished.
  5. Close the fan door.
  6. Verify that the Top Fan Fault LED on the front of the server and the Service Required LEDs on the front and rear of the server are extinguished.
  7. Consider your next step:
    • If you installed the fan module as part of another procedure, return to that procedure.
    • Otherwise, return the server to operation. See Returning the Server to Operation.