Rackmount Checklist
Complete the following checklist prior to installing the server
into a rack or cabinet.
Table 16 Rackmount Checklist
|
|
|
|
|
Is the distance between the front and rear mounting planes between the minimum of 610 mm and
the maximum 915 mm (24 inches to 36 inches)? |
|
|
|
|
Is the clearance depth in the front of the front mounting plane (distance to the front cabinet
door) at least 25.4 mm (1 inch)? |
|
|
|
|
Does the target
rack meet the following minimum load capacity?
|
|
|
|
|
Is the rack
a four-post rack (mounting at both front and rear)?
Two-post racks are not compatible. |
|
|
|
|
Does the rack's
horizontal opening and unit vertical pitch conform to ANSI/EIA 310-D-1992 or
IEC 60927 standards? |
|
|
|
|
Does the rack
have RETMA rail support? |
|
|
|
|
Does the rack
support Oracle cable management arms (CMAs)? |
|
|
|
|
Does the rack
support installation of Oracle vented and solid filler panels? |
|
|
|
|
Can the rack
provide tie-downs for the Ethernet wiring harness? |
|
|
|
|
Is there sufficient
space for the cable harnesses and the power distribution units (PDUs) in
the rack? |
|
|
|
|
Can a label
with the serial number be printed and attached to the target rack? |
|
|
|
|
Does the rack
support installation of standard Oracle PDUs?
If not, then complete this checklist. |
|
|
|
|
Can the customer
provide an equivalent pair of PDUs? |
|
|
|
|
Can the customer
provide two PDUs with capacity of 110kVA per PDU? |
|
|
|
|
Can the customer
provide a single PDU and its circuits to support the power requirements
in case one PDU fails? |
|
|
|
|
Can the customer
ensure power loads are evenly distributed across all circuits of
a single PDU? |
|
|
|
|
Can the customer provide
appropriate power drops for the PDUs? |
|
|
|
|
|