Go to main content
Netra Modular System Installation Guide

Exit Print View

Updated: December 2016
 
 

Environmental Specifications


Caution

Caution  -  Set conditions to the optimal temperature and humidity ranges to minimize downtime due to component failure. Operating the modular system for extended periods at or near the operating range limits, or installing it in an environment where it remains at or near nonoperating range limits, could increase hardware component failure. Operate in the 45 to 50 percent humidity range.


Specification
Operating
Nonoperating
Ambient temperature (does not apply to removable media)
Short-term:

Less than 96 consecutive hours, less than 15 occurrences per year, less than 360 hours per year.

-5 to 50°C
Optimal: 5 to 40°C
For Oracle Server X6-2M, ambient temperature for operation is always limited to 40°C.
-40 to 70°C
Relative humidity
Short-term:5 to 93% noncondensing
Optimal: 5 to 85% noncondensing
5 to 93% noncondensing
Elevation
Up to 10,000 feet at 30°C
Up to 6,000 feet at 40°C
Maximum 39,370 feet
Acoustic noise
Maximum: 9.3 Bels A weighted
Typical: 9 Bels or lower, A weighted
Not applicable
Vibration
0.1G (x,y,z axis) 5 to 100-5Hz swept-sine
Packaged: Oracle 950-1291-01 NEBS GR-63-CORE
Shock
30G's (x,y,z axis) 11 msec half-sine
Packaged: Oracle 950-1291-01 NEBS GR-63-CORE
Earthquake
Zone 4 per NEBS GR-63-CORE Issue 4
Not applicable

Related Information