SPARC S7-2 Server Service Manual

Exit Print View

Updated: March 2017
 
 

Return the Server to the Normal Operating Position


Caution

Caution  -  Deploy any rack anti tilt mechanisms before installing the server into the rack.



Caution

Caution  -  The server weighs approximately 18.1 kg (40.0 lbs). Two people are required to carry the chassis and install it into the rack.


  1. Push the slide rails into the slide rail assemblies in the rack as far as possible.
  2. Raise the server so that the rear ends of the mounting brackets are aligned with the slide rail assemblies that are mounted in the rack.
  3. Insert the mounting brackets into the slide rails, and then push the server into the rack until the mounting brackets encounter the slide rail stops, approximately 30 cm (12 inches).

    The server is now in the extended maintenance position.


    image:Figure that shows how to insert the server into the rack.
    No.
    Description
    1
    Slide rails
    2
    Slide rail release tab (green)
    3
    Slide rail lock
  4. Push the server back into the rack.
    1. Simultaneously pull and hold the two green release tabs (one on each side of the slide rails on the server) toward the front of the server while you push the server into the rack.

      As you push the server into the rack, verify that the CMA retracts without binding.


      Note -  To pull a green release tab, place your finger in the center of the tab, not on the end, and apply pressure as you pull the tab toward the front of the server.

      image:Figure showing the location of the release tabs on the                                     slide rails.
    2. Continue pushing the server into the rack until the slide rail locks (on the front of the server) engage the slide rail assemblies.

      You will hear an audible click when the server is in the normal rack position.

  5. If the CMA is not installed, that is, you removed it because you removed the server completely out of the rack, install the CMA.

    For installation instructions for the CMA, refer to Install the Cable Management Arm in SPARC S7-2 Server Installation Guide.

  6. If the cables are disconnected from the rear of the server, that is, you disconnected the cables because you removed the server completely out of the rack, reconnect the cables.

Related Information