Access Route Guidelines
If your existing loading dock meets height or ramp requirements for a standard freight
carrier truck, you can use a pallet jack to unload the rack. If not, you must provide a
standard forklift or other means to unload the rack, or request the rack be shipped in a
truck with a lift gate.
Leave the rack in its shipping packaging until it reaches its final destination. The
entire access route to the installation site should be free of uneven floor surfaces
that can cause vibration, and the route must meet the requirements listed in the tables
below.
|
|
|
|
|
Minimum door height
|
2184.4 mm
|
86 in.
|
2000 mm
|
78.74 in.
|
Minimum door width
|
1118 mm
|
44 in.
|
600 mm
|
23.62 in.
|
Minimum passage width
|
1220 mm
|
48 in.
|
600 mm
|
26.6 in.
|
Minimum elevator depth
|
1543 mm
|
60.75 in.
|
1058.2 mm
|
41.66 in.
|
|
6˚
|
|
6˚
|
|
|
|
|
Maximum elevator, pallet jack, and floor loading capacity (maximum
weight per rack)
|
1145 kg / 2520 lb maximum weight of rack with full capacity.
Verify weight capacities of elevators and shipping equipment before