Go to main content

Sun Rack II User's Guide

Exit Print View

Updated: July 2018
 
 

Attach a Grounding Cable for TT Power Systems


Caution

Caution  -  When installing the rack in Japan, or other locations that use a TT power systems, you must attach a separate grounding cable to the rack.


  1. Obtain a grounding cable that is at least 6 AWG in size.

    A grounding cable is not shipped with the rack. The minimum supported AWG size is 6.

  2. Attach the grounding cable to the rack grounding terminal using a crimped-on lug suitable to secure the grounding cable to the grounding terminal.

    The rack has a metric M8 stud for its grounding terminal. Securely tighten the crimped-on lug down on the grounding terminal using a lockwasher and nut. The grounding connection must be securely made with clean metal to metal contact.


    image:Figure showing where to install an Earth ground                                 cable.
  3. Attach the other end of the grounding cable to a reliable earthing point in the building using established electrical guidelines and in accordance with electrical codes for the country of installation.

    Caution

    Caution  -  If the installed equipment makes additional connections to earth ground, ensure that all grounding points reference the same earth ground to prevent dangerous ground loops.