Go to main content

SPARC T5-8 Server Installation Guide

Exit Print View

Updated: October 2015
 
 

Electrical Specifications (Half Populated)

Description
Value
Notes
Voltage range
200 to 240 VAC
Frequency
50 to 60 Hz
Maximum operating input current at 200 VAC
(Actual amperage draw may exceed rating by no more than 10%)

The maximum operating input current values are based on P / (V *0.95), where P = max. operating input power, V= input voltage. Example: 1060W / (220V * 0.95) = 5.1A You can use this equation to calculate your maximum operating current at your input voltage.

30A (16A per cord)
Maximum operating input power at 200 VAC
(Actual power draw may exceed rating by no more than 10%)
6000W
Maximum standby power
260W
Idle input power (maximum configuration)

Maximum server configuration specification under nominal temperature and voltage conditions (4 3.6-GHz T5 processors, 128 32-GB DDR3 DIMMS, 8 HDDs, and 16 I/O cards).

1540W
Idle input power (minimum configuration)

Minimum server configuration specification under nominal temperature and voltage conditions (4 3.6-GHz T5 processors, 128 16-GB DDR3 DIMMS, no HDD, and no I/O cards).

1200W
Peak AC input power (maximum configuration)
3680W
Conforms to SpecJBB
Peak AC input power (minimum configuration)
3200W
Conforms to SpecJBB
Maximum heat dissipation
22,185 BTU/hr 23,405 KJ/hr

Caution

Caution  -  Use only the power cords provided with the server.


For information on power specifications, use the power calculator at:

http://www.oracle.com/us/products/servers-storage/sun-power-calculators