Replace a Fiber Cable from FBS to MPO Coupler Panel

This procedure describes how to replace fiber cables from the FBS to the MPO coupler panel.

  1. Follow safety and ESD precautions.

    See Safety and ESD Precautions.

  2. Remove FBS cover at the location of the failed cable.

    See Replace an FBS PCB for FBS cover removal instructions.

  3. Using the label sheet, label the new cable.
  4. Disconnect the faulty cable.
  5. Connect the replacement cable.
  6. Remove the nearby FBS covers, and start laying in the replacement cable bundle, reinstalling FBS covers as you move up the frame.

    See Precautions for Handling Cords and Cables.


    Note -  Leave the faulty cable in place, because it is part of a bundle that has other cables in use on other nodes.
  7. When you have the replacement cable bundle up to the FBS at slot 34, install the remaining FBS covers.
  8. Remove the MPO coupler panel.

    See Remove the MPO Coupler Panel.

  9. Disconnect the faulty cable bundle from the MPO coupler panel.

    Note -  The MPO coupler panel connection is on the side of the coupler panel that faces the front of the modular system. See Rear Components.
  10. Connect the replacement cable bundle to the MPO coupler panel.
  11. Coil up any excess cable.
  12. Install the MPO coupler panel.

    See Install the MPO Coupler Panel.