Rackmount Checklist
Complete the following checklist prior to installing the server into a rack or
cabinet.
|
|
|
|
|
Is the distance between the front and back mounting planes
between the minimum of 610 mm and the maximum 915 mm (24 inches
to 36 inches)?
|
|
|
|
|
Is the clearance depth in the front of the front mounting
plane (distance to the front cabinet door) at least 25.4 mm (1
inch)?
|
|
|
|
|
Does the target rack meet the following minimum load capacity?
|
|
|
|
|
Is the rack a four-post rack (mounting at both front and
back)?
Two-post racks are not compatible.
|
|
|
|
|
Does the rack's horizontal opening and unit vertical pitch
conform to ANSI/EIA 310-D-1992 or IEC 60297 standards?
|
|
|
|
|
Does the rack have RETMA rail support?
|
|
|
|
|
Does the rack support installation of Oracle vented and solid
filler panels?
|
|
|
|
|
Can the rack provide tie-downs for the Ethernet wiring
harness?
|
|
|
|
|
Is there sufficient space for the cable harnesses and the
power distribution units (PDUs) in the rack?
|
|
|
|
|
Can a label with the serial number be printed and attached to
the target rack?
|
|
|
|
|
Does the rack support installation of standard Oracle
PDUs?
If not, then complete this checklist.
|
|
|
|
|
Can the customer provide an equivalent pair of PDUs?
|
|
|
|
|
Can the customer provide two PDUs with capacity of 110kVA per
PDU?
|
|
|
|
|
Can the customer provide a single PDU and its circuits to
support the power requirements in case one PDU fails?
|
|
|
|
|
Can the customer ensure power loads are evenly distributed
across all circuits of a single PDU?
|
|
|
|
|
Can the customer provide appropriate power drops for the
PDUs?
|
|
|
|
|
|