Rackmount Checklist

Complete the following checklist prior to installing the server into a rack or cabinet.

Rackmount Considerations
Yes
No
N/A
Comment
Is the distance between the front and back mounting planes between the minimum of 610 mm and the maximum 915 mm (24 inches to 36 inches)?
Is the clearance depth in the front of the front mounting plane (distance to the front cabinet door) at least 25.4 mm (1 inch)?
Does the target rack meet the following minimum load capacity?
  • 19 kg/U

  • 785 kg total

Is the rack a four-post rack (mounting at both front and back)?
Two-post racks are not compatible.
Does the rack's horizontal opening and unit vertical pitch conform to ANSI/EIA 310-D-1992 or IEC 60297 standards?
Does the rack have RETMA rail support?
Does the rack support installation of Oracle vented and solid filler panels?
Can the rack provide tie-downs for the Ethernet wiring harness?
Is there sufficient space for the cable harnesses and the power distribution units (PDUs) in the rack?
Can a label with the serial number be printed and attached to the target rack?
Does the rack support installation of standard Oracle PDUs?
If not, then complete this checklist.
Can the customer provide an equivalent pair of PDUs?
Can the customer provide two PDUs with capacity of 110kVA per PDU?
Can the customer provide a single PDU and its circuits to support the power requirements in case one PDU fails?
Can the customer ensure power loads are evenly distributed across all circuits of a single PDU?
Can the customer provide appropriate power drops for the PDUs?