Electrical Requirements

Oracle Server X7-8 uses AC power. The following table contains the power supply specifications.


Note -  The power dissipation numbers listed in the following table are the maximum rated power numbers for the power supply used in the system. The numbers are not a rating of the actual power consumption of the system. For up-to-date information on power consumption, go to the Oracle Power Calculators web site http://www.oracle.com/us/products/servers-storage/sun-power-calculators/index.html, and click the Oracle Server X7-8 link.
Parameter
Specification
Voltage (nominal)
200-240 VAC
Input current (maximum)
  • 23A @ 200 to 240 VAC

  • 12A max per cord

Frequency (nominal)
50/60 Hz
Maximum power consumption
  • Single 4-socket –1980 W

  • Dual 4-socket – 3950 W

  • Single 8-socket – 3880 W

Maximum heat output
13475 BTU/Hr

Your Oracle Server X7-8 can operate effectively over a range of voltages and frequencies.


Caution

Caution  -  The system must have a reliable power source. If the system exceeds the voltage and frequency ranges, damage to the server might occur. Electrical disturbances, such as the following, might damage the system:

  • Fluctuations caused by brownouts
  • Wide and rapid variations in input voltage levels or in input power frequency
  • Electrical storms
  • Faults in the distribution system, such as defective wiring


To protect your server from disturbances, use a dedicated power distribution system, power-conditioning equipment, and lightning arresters or power cables to protect from electrical storms.