Go to main content

Oracle® Server X7-8 Installation Guide

Exit Print View

Updated: April 2018
 
 

Environmental Requirements

The following table lists the specifications for temperature, humidity, altitude, acoustic noise, vibration, and shock.


Caution

Caution  -  Set conditions to the optimal temperature and humidity ranges to minimize the chance of downtime due to component failure. Operating your Oracle Server X7-8 for extended periods at or near the operating range limits, or installing it in an environment when it remains at or near nonoperating range limits could significantly increase hardware component failure.


Specification
Operating
Nonoperating
Ambient temperature (Does not apply to removable media)
  • 41˚F to 95˚F (5˚C to 35˚C) up to 2,953 feet (900 meters)

  • Optimal: 69.8˚F to 73.4˚F (21˚C to 23˚C)

Note -  Maximum ambient operating temperature is derated by 1 degree C per every 300 meters elevation beyond 900 meters, up to a maximum altitude of 3,000 meters elevation.

–40˚F to 154˚F (–40˚C to 68˚C)
Relative humidity
  • 10% to 90% noncondensing, short term 25˚F to 113˚F (–5˚C to 55˚C)

  • 5% to 90% noncondensing, but not to exceed 0.024 kg of water per kg of dry air (0.053 lbs water/2.205 lbs dry air)

Up to 93% noncondensing 95˚F (35˚C) maximum wet bulb
Altitude
Maximum 9,840 feet (3,000 meters) at 95˚F (35˚C)

Note -  In China markets, regulations might limit installations to a maximum altitude of 6,562 feet (2,000 meters).

Maximum 39,370 feet (12,000  meters)
Acoustic Noise
  • Maximum condition: 8.1 Bels

  • Idle condition: 5.8 Bels

Not applicable
Vibration
  • 0.15 G (z-axis)

  • 0.10 G (x-, y-axes), 5-500Hz swept sine

IEC 60068-2-6 Test FC
  • 0.5 G (z-axis)

  • 0.25 G (x-, y-axes), 5-500Hz swept sine

IEC 60068-2-6 Test FC
Shock
3 Gs, 11 ms half-sine
IEC 60068-2-27 Test Ea
Roll-off: 1.25-inch roll-off free fall, front to back rolling directions
Threshold: 13 mm threshold height at 0.65 m/s impact velocity
ETE-1010-02 Rev A

Related Information