Go to main content

Oracle® Server X7-8 Installation Guide

Exit Print View

Updated: April 2018
 
 

Rack Compatibility

The rack into which you install Oracle Server X7-8 must meet the requirements listed in the following table. The Oracle Rack Cabinet 1242 and Oracle's Sun Rack II Cabinet are compatible with the server. For information on these Oracle racks, see Preparing for Server Installation.

Item
Requirement
Structure
Four-post rack (mounting at both front and back) with 9.5mm square holes.
Two-post racks are not compatible.
Rack horizontal opening and unit vertical pitch
Conforms to ANSI/EIA 310-D-1992 or IEC 60297 standards.
Distance between front and back mounting planes
Minimum 61 cm and maximum 91.5 cm (24 inches to 36 inches).
Clearance depth in front of front mounting plane
Distance to front cabinet door is at least 2.54 cm (1 inch).
Clearance depth behind front mounting plane
Distance to back cabinet door is at least 80 cm (31.49 inches).
Clearance width between front and back mounting planes
Distance between structural supports and cable troughs is at least 45.6 cm (18 inches).
Minimum clearance for service access
  • Clearance, front of server: 123.2 cm (48.5 inches)

  • Clearance, back of server: 91.4 cm (36 inches)

The following table lists the Oracle Rack Cabinet 1242 rack specifications:

Requirement
Specification
Usable rack units
42
Height
199. cm (78.74 inches)
Width (with side panels)
60 cm (23.62 inches)
Maximum dynamic load
1005 kg (2215 lbs)

Related Information