Seven-Rack Cabling

The following table shows the cable connections for the first spine switch (R1-U1) when cabling seven full racks together.

Table 44  Leaf Switch Connections for the First Rack in a Seven-Rack System
Leaf Switch
Connection
Cable Length
R1 U24 within Rack 1
R1-U24-P8A to R1-U1-P3A
R1-U24-P8B to R1-U1-P4A
3 meters
R1 U24 to Rack 2
R1-U24-P9A to R2-U1-P5A
5 meters
R1 U24 to Rack 3
R1-U24-P9B to R3-U1-P6A
5 meters
R1 U24 to Rack 4
R1-U24-P10A to R4-U1-P7A
10 meters
R1 U24 to Rack 5
R1-U24-P10B to R5-U1-P8A
10 meters
R1 U24 to Rack 6
R1-U24-P11A to R6-U1-P9A
10 meters
R1 U24 to Rack 7
R1-U24-P11B to R7-U1-P10A
10 meters
R1 U18 within Rack 1
R1-U18-P8A to R1-U1-P3B
R1-U18-P8B to R1-U1-P4B
3 meters
R1 U18 to Rack 2
R1-U18-P9A to R2-U1-P5B
5 meters
R1 U18 to Rack 3
R1-U18-P9B to R3-U1-P6B
5 meters
R1 U18 to Rack 4
R1-U18-P10A to R4-U1-P7B
10 meters
R1 U18 to Rack 5
R1-U18-P10B to R5-U1-P8B
10 meters
R1 U18 to Rack 6
R1-U18-P11A to R6-U1-P9B
10 meters
R1 U18 to Rack 7
R1-U18-P11B to R7-U1-P10B
10 meters

The following table shows the cable connections for the second spine switch (R2-U1) when cabling seven full racks together.

Table 45  Leaf Switch Connections for the Second Rack in a Seven-Rack System
Leaf Switch
Connection
Cable Length
R2 U24 within Rack 2
R2-U24-P8A to R2-U1-P3A
R2-U24-P8B to R2-U1-P4A
3 meters
R2 U24 to Rack 1
R2-U24-P11B to R1-U1-P10A
5 meters
R2 U24 to Rack 3
R2-U24-P9A to R3-U1-P5A
5 meters
R2 U24 to Rack 4
R2-U24-P9B to R4-U1-P6A
5 meters
R2 U24 to Rack 5
R2-U24-P10A to R5-U1-P7A
10 meters
R2 U24 to Rack 6
R2-U24-P10B to R6-U1-P8A
10 meters
R2 U24 to Rack 7
R2-U24-P11A to R7-U1-P9A
10 meters
R2 U18 within Rack 2
R2-U18-P8A to R2-U1-P3B
R2-U18-P8B to R2-U1-P4B
3 meters
R2 U18 to Rack 1
R2-U18-P11B to R1-U1-P10B
5 meters
R2 U18 to Rack 3
R2-U18-P9A to R3-U1-P5B
5 meters
R2 U18 to Rack 4
R2-U18-P9B to R4-U1-P6B
5 meters
R2 U18 to Rack 5
R2-U18-P10A to R5-U1-P7B
10 meters
R2 U18 to Rack 6
R2-U18-P10Bto R6-U1-P8B
10 meters
R2 U18 to Rack 7
R2-U18-P11A to R7-U1-P9B
10 meters

The following table shows the cable connections for the third spine switch (R3-U1) when cabling seven full racks together.

Table 46  Leaf Switch Connections for the Third Rack in a Seven-Rack System
Leaf Switch
Connection
Cable Length
R3 U24 within Rack 3
R3-U24-P8A to R3-U1-P3A
R3-U24-P8B to R3-U1-P4A
3 meters
R3 U24 to Rack 1
R3-U24-P11A to R1-U1-P9A
5 meters
R3 U24 to Rack 2
R3-U24-P11B to R2-U1-P10A
5 meters
R3 U24 to Rack 4
R3-U24-P9A to R4-U1-P5A
5 meters
R3 U24 to Rack 5
R3-U24-P9B to R5-U1-P6A
5 meters
R3 U24 to Rack 6
R3-U24-P10A to R6-U1-P7A
10 meters
R3 U24 to Rack 7
R3-U24-P10B to R7-U1-P8A
10 meters
R3 U18 within Rack 3
R3-U18-P8A to R3-U1-P3B
R3-U18-P8B to R3-U1-P4B
3 meters
R3 U18 to Rack 1
R3-U18-P11A to R1-U1-P9B
5 meters
R3 U18 to Rack 2
R3-U18-P11B to R2-U1-P10B
5 meters
R3 U18 to Rack 4
R3-U18-P9A to R4-U1-P5B
5 meters
R3 U18 to Rack 5
R3-U18-P9B to R5-U1-P6B
5 meters
R3 U18 to Rack 6
R3-U18-P10A to R6-U1-P7B
10 meters
R3 U18 to Rack 7
R3-U18-P10B to R7-U1-P8B
10 meters

The following table shows the cable connections for the fourth spine switch (R4-U1) when cabling seven full racks together.

Table 47  Leaf Switch Connections for the Fourth Rack in a Seven-Rack System
Leaf Switch
Connection
Cable Length
R4 U24 within Rack 4
R4-U24-P8A to R4-U1-P3A
R4-U24-P8B to R4-U1-P4A
3 meters
R4 U24 to Rack 1
R4-U24-P10B to R1-U1-P8A
10 meters
R4 U24 to Rack 2
R4-U24-P11A to R2-U1-P9A
5 meters
R4 U24 to Rack 3
R4-U24-P11B to R3-U1-P10A
5 meters
R4 U24 to Rack 5
R4-U24-P9A to R5-U1-P5A
5 meters
R4 U24 to Rack 6
R4-U24-P9B to R6-U1-P6A
5 meters
R4 U24 to Rack 7
R4-U24-P10A to R7-U1-P7A
10 meters
R4 U18 within Rack 4
R4-U18-P8A to R4-U1-P3B
R4-U18-P8B to R4-U1-P4B
3 meters
R4 U18 to Rack 1
R4-U18-P10B to R1-U1-P8B
10 meters
R4 U18 to Rack 2
R4-U18-P11A to R2-U1-P9B
5 meters
R4 U18 to Rack 3
R4-U18-P11B to R3-U1-P10B
5 meters
R4 U18 to Rack 5
R4-U18-P9A to R5-U1-P5B
5 meters
R4 U18 to Rack 6
R4-U18-P9B to R6-U1-P6B
5 meters
R4 U18 to Rack 7
R4-U18-P10A to R7-U1-P7B
10 meters

The following table shows the cable connections for the fifth spine switch (R5-U1) when cabling seven full racks together.

Table 48  Leaf Switch Connections for the Fifth Rack in a Seven-Rack System
Leaf Switch
Connection
Cable Length
R5 U24 within Rack 5
R5-U24-P8A to R5-U1-P3A
R5-U24-P8B to R5-U1-P4A
3 meters
R5 U24 to Rack 1
R5-U24-P10A to R1-U1-P7A
10 meters
R5 U24 to Rack 2
R5-U24-P10B to R2-U1-P8A
10 meters
R5 U24 to Rack 3
R5-U24-P11A to R3-U1-P9A
5 meters
R5 U24 to Rack 4
R5-U24-P11B to R4-U1-P10A
5 meters
R5 U24 to Rack 6
R5-U24-P9A to R6-U1-P5A
5 meters
R5 U24 to Rack 7
R5-U24-P9B to R7-U1-P6A
5 meters
R5 U18 within Rack 5
R5-U18-P8A to R5-U1-P3B
R5-U18-P8B to R5-U1-P4B
3 meters
R5 U18 to Rack 1
R5-U18-P10A to R1-U1-P7B
10 meters
R5 U18 to Rack 2
R5-U24-P10B to R2-U1-P8B
10 meters
R5 U18 to Rack 3
R5-U18-P11A to R3-U1-P9B
5 meters
R5 U18 to Rack 4
R5-U18-P11B to R4-U1-P10B
5 meters
R5 U18 to Rack 6
R5-U18-P9A to R6-U1-P5B
5 meters
R5 U18 to Rack 7
R5-U18-P9B to R7-U1-P6B
5 meters

The following table shows the cable connections for the sixth spine switch (R6-U1) when cabling seven full racks together.

Table 49  Leaf Switch Connections for the Sixth Rack in a Seven-Rack System
Leaf Switch
Connection
Cable Length
R6 U24 within Rack 6
R6-U24-P8A to R6-U1-P3A
R6-U24-P8B to R6-U1-P4A
3 meters
R6 U24 to Rack 1
R6-U24-P9B to R1-U1-P6A
10 meters
R6 U24 to Rack 2
R6-U24-P10A to R2-U1-P7A
10 meters
R6 U24 to Rack 3
R6-U24-P10B to R3-U1-P8A
5 meters
R6 U24 to Rack 4
R6-U24-P11A to R4-U1-P9A
5 meters
R6 U24 to Rack 5
R6-U24-P11B to R5-U1-P10A
5 meters
R6 U24 to Rack 7
R6-U24-P9A to R7-U1-P5A
5 meters
R6 U18 within Rack 6
R6-U18-P8A to R6-U1-P3B
R6-U18-P8B to R6-U1-P4B
3 meters
R6 U18 to Rack 1
R6-U18-P9B to R1-U1-P6B
10 meters
R6 U18 to Rack 2
R6-U24-P10A to R2-U1-P7B
10 meters
R6 U18 to Rack 3
R6-U18-P10B to R3-U1-P8B
5 meters
R6 U18 to Rack 4
R6-U18-P11A to R4-U1-P9B
5 meters
R6 U18 to Rack 5
R6-U18-P11B to R5-U1-P10B
5 meters
R6 U18 to Rack 7
R6-U24-P9A to R7-U1-P5B
5 meters

The following table shows the cable connections for the seventh spine switch (R7-U1) when cabling seven full racks together.

Table 50  Leaf Switch Connections for the Seventh Rack in a Seven-Rack System
Leaf Switch
Connection
Cable Length
R7 U24 within Rack 7
R7-U24-P8A to R7-U1-P3A
R7-U24-P8B to R7-U1-P4A
3 meters
R7 U24 to Rack 1
R7-U24-P9A to R1-U1-P5A
10 meters
R7 U24 to Rack 2
R7-U24-P9B to R2-U1-P6A
10 meters
R7 U24 to Rack 3
R7-U24-P10A to R3-U1-P7A
10 meters
R7 U24 to Rack 4
R7-U24-P10B to R4-U1-P8A
10 meters
R7 U24 to Rack 5
R7-U24-P11A to R5-U1-P9A
5 meters
R7 U24 to Rack 6
R7-U24-P11B to R6-U1-P10A
5 meters
R7 U18 within Rack 7
R7-U18-P8A to R7-U1-P3B
R7-U18-P8B to R7-U1-P4B
3 meters
R7 U18 to Rack 1
R7-U18-P9A to R1-U1-P5B
10 meters
R7 U18 to Rack 2
R7-U24-P9B to R2-U1-P6B
10 meters
R7 U18 to Rack 3
R7-U18-P10A to R3-U1-P7B
10 meters
R7 U18 to Rack 4
R7-U18-P10B to R4-U1-P8B
10 meters
R7 U18 to Rack 5
R7-U18-P11A to R5-U1-P9B
5 meters
R7 U18 to Rack 6
R7-U24-P11B to R6-U1-P10B
5 meters