PDU Power Requirements
When ordering the Oracle Exadata Storage Expansion Rack, you must provide two specifications:
Refer to the following tables for Oracle marketing and manufacturing part
numbers.
Note -
Each Oracle Exadata Storage Expansion Rack has two power distribution units (PDUs). Both PDUs
in a rack must be the same type.
Table 62 PDU Choices
|
|
|
Low
|
1
|
|
Low
|
3
|
|
High
|
1
|
|
High
|
3
|
|
|
Table 63 Low Voltage 1 Phase PDUs for Oracle Exadata Storage Expansion Rack
|
|
|
kVA Size
|
15 kVA
|
|
Marketing part number
|
N/A
|
|
Manufacturing part number
|
N/A
|
|
Phase
|
1 ph
|
|
Voltage
|
200 to 240 VAC
|
|
Amps per PDU
|
72 A (3 inputs x 24 A)
|
|
Outlets
|
42 C13
6 C19
|
|
Number of inputs
|
3 inputs
|
|
Input current
|
24 A max. per input
|
|
Data center receptacle
|
NEMA 30A/250 VAC 2-pole/3-wire L6-30P
|
|
Outlet groups per PDU
|
6
|
|
Usable PDU power cord length
|
2 m (6.6 feet)
|
PDU power cords are 4 m long (13 feet), but sections are
used for internal routing in the rack.
|
|
Table 64 Low Voltage 3 Phase PDUs for Oracle Exadata Storage Expansion Rack
|
|
|
kVA Size
|
14.4 kVA
|
|
Marketing part number
|
N/A
|
|
Manufacturing part number
|
N/A
|
|
Phase
|
3 ph
|
|
Voltage
|
190 to 220 VAC
|
|
Amps per PDU
|
69 A (3 inputs x 23 A)
|
|
Outlets
|
42 C13
6 C19
|
|
Number of inputs
|
2 inputs x 60 A, 3 ph
|
|
Input current
|
40 A max. per phase
|
|
Data center receptacle
|
IEC 60309 60A 4-pin 250 VAC 3 ph IP 67
|
|
Outlet groups per PDU
|
6
|
|
Usable PDU power cord length
|
2 m (6.6 feet)
|
PDU power cords are 4 m long (13 feet), but sections are
used for internal routing in the rack.
|
|
Table 65 High Voltage 1 Phase PDUs for Oracle Exadata Storage Expansion Rack
|
|
|
kVA Size
|
15 kVA
|
|
Marketing part number
|
N/A
|
|
Manufacturing part number
|
N/A
|
|
Phase
|
1 ph
|
|
Voltage
|
220 to 240 VAC
|
|
Amps per PDU
|
72 A (3 inputs x24 A)
|
|
Outlets
|
42 C13
6 C19
|
|
Number of inputs
|
6
|
|
Input current
|
25 A max. per input
|
|
Data center receptacle
|
IEC 60309 32A 3-pin 250VAC IP44
|
|
Outlet groups per PDU
|
6
|
|
Usable PDU power cord length
|
2 m (6.6 feet)
|
PDU power cords are 4 m long (13 feet), but sections are
used for internal routing in the rack.
|
|
Table 66 High Voltage 3 Phase PDUs for Oracle Exadata Storage Expansion Rack
|
|
|
kVA size
|
14.4 kVA
|
|
Marketing part number
|
N/A
|
|
Manufacturing part number
|
N/A
|
|
Phase
|
3 ph
|
|
Voltage
|
220/380 to 240/415 VAC
|
|
Amps per PDU
|
62.7 A (3 inputs x 20.9. A)
|
|
Outlets
|
42 C13
6 C19
|
|
Number of inputs
|
2 inputs x 25 A
|
|
Input current
|
25 A max. per phase
|
|
Data center receptacle
|
IEC 60309 32A, 5-pin 230/400 VAC
|
|
Outlet groups per PDU
|
6
|
|
Usable PDU power cord length
|
2 m (6.6 feet)
|
PDU power cords are 4 m long (13 feet), but sections are
used for internal routing in the rack.
|
|