SPARC SuperCluster T4-4 Owner's Guide

Exit Print View

Updated: February 2016
 
 

PDU Power Requirements

When ordering SPARC SuperCluster T4-4 you selected one of these options:

  • Low or high voltage

  • Single or three phase power

Refer to the following tables for Oracle marketing and manufacturing part numbers.


Note -  Each SPARC SuperCluster T4-4 has two power distribution units (PDUs). Both PDUs in a rack must be the same type.
Table 6  PDU Choices
Voltage
Phases
Reference
Low
1
Low
3
High
1
High
3
Table 7  Low Voltage 1 Phase PDUs for SPARC SuperCluster T4-4
Low Voltage
Single Phase
Comments
kVA Size
22 kVA
Marketing part number
7100873
Manufacturing part number
7018123
Phase
1 ph
Voltage
200-240 VAC
Amps per PDU
110.4A (3 inputs x 36.8A)
Outlets
42 C13
6 C19
Number of inputs
3 inputs x50A, 1 ph
Input current
36.8A max. current (per input)
Data center receptacle
Hubbell CS8264C
Outlet groups per PDU
6
Usable PDU power cord length
2 m (6.6 feet)
PDU power cords are 4 m long (13 feet), but sections are used for internal routing in the rack.
Table 8  Low Voltage 3 Phase PDUs for SPARC SuperCluster T4-4
Low Voltage
Three Phase
Comments
kVA Size
24 kVA
Marketing part number
6444A
Manufacturing part number
597-1162-01
Phase
3 ph
Voltage
200 to 240 VAC
Amps per PDU
120A (6 x 20A)
Outlets
42 C13
6 C19
Number of inputs
2 inputs x 60A, 3 ph
Input current
34.6 A max. per phase
Data center receptacle
IEC 309-3P4W-IP67
(60A, 250V, AC, 3 ph)
Outlet groups per PDU
Hubbell HBL460R/C9W or equivalent
IEC309 60A 3ph 4 Wire
Usable PDU power cord length
4
kVA Size
2 m (6.6 feet)
PDU power cords are 4 m long (13 feet), but sections are used for internal routing in the rack.
Table 9  High Voltage 1 Phase PDUs for SPARC SuperCluster T4-4
High Voltage
Single Phase
Comments
kVA Size
22 kVA
Marketing part number
7100874
Manufacturing part number
7018124
Phase
1 ph
Voltage
200 to 240 VAC
Amps per PDU
96A (3 inputs x 32A)
Outlets
42 C13
6 C19
Number of inputs
3 inputs x 32A, 1 ph
Input current
32A max. per input
Data center receptacle
IEC 309-2P3W-IP44
(32A, 250V, AC, 3 ph)
Outlet groups per PDU
Hubbell HBL332R/C9W or equivalent
IEC309 32A 1 ph 3 Wire
Usable PDU power cord length
6
kVA Size
2 m (6.6 feet)
PDU power cords are 4 m long (13 feet), but sections are used for internal routing in the rack.
Table 10  High Voltage 3 Phase PDUs for SPARC SuperCluster T4-4
High Voltage
Three Phase
Comments
kVA Size
24 kVA
Marketing part number
6445A
Manufacturing part number
597-1163-01
Phase
3 ph
Voltage
220/380 to 240/415 VAC
Amps per PDU
109A (6 inputs x 18.1A)
Outlets
42 C13
6 C19
Number of inputs
2 inputs x25A, 3 ph
Input current
18 A max. per input
Data center receptacle
IEC 309-4P5W-IP44
(32A, 400V, AC, 3 ph)
Outlet groups per PDU
Hubbell HBL532R/C9W or equivalent.
IEC309 32A 3ph 5 Wire
Usable PDU power cord length
4
kVA Size
2 m (6.6 feet)
PDU power cords are 4 m long (13 feet), but sections are used for internal routing in the rack.