Troubleshooting Using the Server Front and Back Panel Status Indicators
            These sections describe the status indicators (LEDs) located on the front and back
                of the server, including those found on components and ports. This section includes
                the following topics:
            
            
                Related Information
                
            
            
                Server Boot Process and Normal Operating State Indicators
                
                    
                    
                
                A normal server boot process involves two indicators, the service processor SP
                    OK LED indicator and the System OK LED indicator.
                When you connect AC power to the server, the server boots into standby power
                    mode:
                
                    - 
                        The SP OK LED blinks slowly (0.5 seconds on, 0.5 seconds off) while
                            the SP is starting, and the main System OK LED remains off until the SP
                            is ready. 
- 
                        After a few minutes, the main System OK LED slowly flashes the standby
                            blink pattern (0.1 seconds on, 2.9 seconds off), indicating that the SP
                            is ready for use. In Standby power mode, the server is not initialized
                            or fully powered on at this point. 
When powering on the server (either by the On/Standby button or Oracle ILOM),
                    the server boots to Main power mode:
                
                    - 
                        The System OK LED blinks slowly (0.5 seconds on, 0.5 seconds off), and
                            the SP OK LED remains lit (no blinking). 
- 
                        When the server successfully boots, the System OK LED remains lit.
                            When the System OK LED and the SP OK LED indicators remain lit, the
                            server is in Main power mode. 
Note - 
                    The green System OK LED indicator and the green SP OK indicator remain lit
                        (no blinking) when the server is in a normal operating state.
                
            
            
                Server System-Level Status Indicators
                
                    
                    
                
                
                    
                
                
                    
                
                
                    
                
                
                    
                
                
                    
                
                There are seven system-level status indicators (LEDs), some of which are
                    located on both the server front panel and the back panel. For the location of
                    the status indicators, see Front and Back Panel Components. The following table describes these indicators.
                
                    
                    | 
                        
                        
                        
                        
                        
                            
                                |  |  |  |  |  
                                | Locate Button/LED |   | White | Indicates the location of the server. 
                                        
                                            FAST BLINK (250 ms) – Use Oracle ILOM to
                                                activate this LED indicator to enable you to locate
                                                a particular system quickly and easily.
                                            Pressing the Locate button toggles the LED
                                                indicator fast blink on or off. |  
                                | Fault-Service Required |   | Amber | Indicates the fault state of the server. Note - 
                                        When this LED indicator is lit, a system console
                                            message might appear that includes a recommended service
                                            action.
                                     |  
                                | System OK |   | Green | Indicates the operational state of the chassis. 
                                        
                                            OFF – AC power is not present or the Oracle
                                                ILOM boot is not complete.
                                            STANDBY BLINK (on for 100 ms, off for 2900 ms)
                                                – Standby power is on, but the chassis power
                                                is off and the Oracle ILOM SP is running.
                                            SLOW BLINK (1000 ms) – Startup sequence was
                                                initiated on the host. This pattern begins soon
                                                after you power on the server. This status indicates
                                                either: power-on self-test (POST) code checkpoint
                                                tests are running on the server host system, or the
                                                host is transitioning from the powered-on state to
                                                the standby state on shutdown.
                                            STEADY ON – The server is powered on, and
                                                all host POST code checkpoint tests are complete.
                                                The server is in one of the following states: the
                                                server host is booting the operating system (OS), or
                                                the server host is running the OS. |  
                                | SP OK |   | Green | Indicates the state of the service processor. 
                                        
                                            OFF – Service processor (SP) is not
                                                running.
                                            SLOW BLINK – SP is booting.
                                            STEADY ON – SP is fully operational. |  
                                | Top Fan |   | Amber | Indicates that one or more of the internal fan modules
                                        failed. |  
                                | Back Power Supply Fault |   Back | Amber | Indicates that one of the server power supplies
                                        failed. |  
                                | System Over Temperature Warning |   | Amber | Indicates a warning for an overtemperature
                                        condition. Note - 
                                        This is a warning indication, not a fatal
                                            overtemperature. Failure to correct this might result in
                                            the system overheating and shutting down
                                            unexpectedly.
                                     |  
                                | DO NOT SERVICE |   | White | Indicates that the system is not ready to service. Note - 
                                        The DO NOT SERVICE indicator is application specific.
                                            This indicator is illuminated only on demand by the Host
                                            application.
                                     |  | 
                
            
            
                Server Fan Status Indicators
                
                    
                    
                
                
                    
                    
                
                Each fan module has one status indicator (LED). The LEDs are located on the
                    chassis mid-wall adjacent to and aligned with the fan modules, and are visible
                    when the server top cover is removed.
                
                    
                    | 
                        
                        
                        
                        
                        
                            
                                |  |  |  |  |  
                                | Fan Status |   | Amber | 
                                        
                                            Off – The fan module is correctly installed
                                                and operating within specification.
                                            Amber – The fan module is faulty. The front
                                                TOP FAN LED and the front and back panel
                                                Fault-Service Required LEDs are also lit if the
                                                system detects a fan module fault. |  | 
                
            
            
                Storage Drive Status Indicators
                
                    
                    
                
                
                    
                    
                
                
                    
                    
                
                
                    
                    
                
                
                    
                    
                
                There are three status indicators (LEDs) on each drive, which applies to only
                    the HC server.
                
                    
                    | 
                        
                        
                        
                        
                        
                            
                                |  |  |  |  |  
                                | OK/Activity |   | Green | 
                                        
                                            OFF – Power is off or installed drive is not
                                                recognized by the system.
                                            STEADY ON – The drive is engaged and is
                                                receiving power.
                                            RANDOM BLINK – There is disk activity.
                                                Status indicator LED blinks on and off to indicate
                                                activity. |  
                                | Fault-Service Required |   | Amber |  |  
                                | OK to Remove |   | Blue |  |  | 
                
            
            
                Power Supply Status Indicators
                
                    
                    
                
                
                    
                    
                
                There are two status indicators (LEDs) on each power supply. These indicators
                    are visible from the back of the server.
                
                    
                    | 
                        
                        
                        
                        
                        
                            
                                |  |  |  |  |  
                                | AC OK/ DC OK |   | Green | 
                                        
                                            OFF – No AC power is present.
                                            SLOW BLINK – Normal operation. Input power
                                                is within specification. DC output voltage is not
                                                enabled.
                                            STEADY ON – Normal operation. Input AC power
                                                and DC output voltage are within
                                                specification. |  
                                | Fault-Service Required |   | Amber | 
                                        
                                            OFF – Normal operation. No service action is
                                                required.
                                            STEADY ON – The power supply (PS) detected a
                                                PS fan failure, PS overtemperature, PS over current,
                                                or PS over or under voltage. |  | 
                
            
            
                Network Management Port Status Indicators
                
                    
                    
                
                
                    
                    
                
                The server has one 10/100/1000BASE-T Ethernet management domain interface,
                    labeled NET MGT. There are two status indicators (LEDs) on this port. These
                    indicators are visible from the back of the server.
                
                    
                    | 
                        
                        
                        
                        
                        
                            
                                |  |  |  |  |  
                                | Activity | Top left | Green |  |  
                                | Link speed | Top right | Green | 
                                        
                                            ON – 1000BASE-T link.
                                            OFF – 10/100BASE-T link. |  | 
                
            
            
                Ethernet Port Status Indicators
                
                    
                    
                
                
                    
                    
                
                
                    
                    
                
                The server has one Gigabit Ethernet port (NET 0). There are two status
                    indicators (LEDs) that are visible from the back of the server.
                
                    
                    | 
                        
                        
                        
                        
                        
                            
                                |  |  |  |  |  
                                | Activity | Bottom left | Green |  |  
                                | Link speed | Bottom right | Bi-colored: Amber/Green |  |  | 
                
            
            
                Motherboard Status Indicators
                
                    
                    
                
                
                    
                    
                
                The motherboard contains the following status indicators (LEDs).
                
                    
                    | 
                        
                        
                        
                            
                                |  |  |  
                                | DIMM Fault Status Indicators | 
                                        
                                            Each 24 DIMM socket on the motherboard has an
                                                amber fault status indicator (LED) associated with
                                                it.
                                            If Oracle ILOM determines that a DIMM is faulty,
                                                pressing the Fault Remind button on the motherboard
                                                I/O card signals the service processor to light the
                                                fault LED associated with the failed DIMM. 
                                            For more information on DIMM fault status
                                                indicators and the location of the Fault Remind
                                                button, see Servicing the DIMMs. |  
                                | Processor Fault Status Indicators | 
                                        
                                            The motherboard includes a fault status indicator
                                                (LED) adjacent to each of the two processor
                                                sockets.
                                            These LEDs indicate when a processor fails.
                                            Pressing the Fault Remind button on the
                                                motherboard I/O card signals the service processor
                                                to light the fault status indicators associated with
                                                the failed processors.
                                            For more information on processor fault status
                                                indicators and the location of the Fault Remind
                                                button, see Servicing Processors. |  
                                | Fault Remind Status Indicator | 
                                        
                                            This status indicator (LED) is located next to the
                                                Fault Remind button and is powered from the super
                                                capacitor that powers the fault LEDs on the
                                                motherboard.
                                            This LED lights to indicate that the fault remind
                                                circuitry is working properly in cases where no
                                                components failed and, as a result, none of the
                                                component fault LEDs illuminate.
                                            For more information on the fault remind status
                                                indicator and the location of the Fault Remind
                                                button, see Using the Server Fault Remind Button. |  
                                | STBY PWRGD Status Indicator | 
                                        
                                            This green status indicator (LED) is labeled STBY
                                                PWRGD and is located on the motherboard near the
                                                back of the server.
                                            This LED lights to inform a service technician
                                                that the motherboard is receiving Standby power from
                                                at least one of the power supplies. 
                                            This LED helps prevent service actions on the
                                                server internal components while the AC power cords
                                                are installed and power is supplied to the
                                                server. |  
                                | PCIe Hot-Plug Status Indicators | 
                                        
                                            Each PCIe card on the motherboard has a green
                                                power indicator and an amber attention status
                                                indicator (LED) associated with it.
                                            If the green power LED is on and the amber
                                                attention LED is off, then the SSD is operating
                                                properly.
                                            If the amber attention LED is on, verify the state
                                                of the SSD in the Oracle Exadata Storage Server Cell
                                                Software to determine if the PCIe card is faulty and
                                                needs replacement. |  |