PDU Power Requirements

When ordering the system you selected one of these options:

  • Low or high voltage

  • Single or three phase power

Refer to the following tables for Oracle marketing and manufacturing part numbers.


Note - Each system has two power distribution units (PDUs). Both PDUs in a rack must be the same type.
Table 6  PDU Choices
Voltage
Phases
Reference
Low
2
Low
3
High
1
High
3
Table 7  Low Voltage 2 Phase PDUs
Low Voltage
Dual Phase (2W+GND)
Comments
kVA Size
22 kVA
Marketing part number
7100873
Manufacturing part number
7018123
Phase
2
No Grounded Neutral provided in input cords
Voltage input rating
3x [2Ph. (2W+ground)] 208 Vac, 50/60 Hz, max. 36.8A per phase
Can be connected to Ph-Ph input sources in range of 200V - 240V AC nominal
Amps per PDU
110.4A (3 inputs x 36.8A)
Outlets
42 C13
6 C19
Number of inputs
3 inputs x50A plug, 2Ph (2W+ground)
3 inputs/plugs per PDU, or 6 total inputs/plugs for system
Input current
36.8A max. current (per input)
Data center receptacle
Hubbell CS8264C
Outlet groups per PDU
6
Usable PDU power cord length
2 m (6.6 feet)
PDU power cords are 4 m long (13 feet), but sections are used for internal routing in the rack.
Summary:
Number of PDUs in Oracle SuperCluster T5-8: 2
Number of circuits per PDU: 3 @ 50A 2-phase 208V
Total number of circuits required: 6 @ 50A 2-phase 208V (2 per PDU)
Total number of data center receptacles required: 6 x Hubbell CS8264C
Total Amps per PDU: 110.4A 2-phase 208V
Total Amps for entire Oracle SuperCluster T5-8: 220.8A 2-phase 208V (2 PDUs @ 110.4A 2-phase 208V each)
Table 8  Low Voltage 3 Phase PDUs
Low Voltage
Three Phase (3W+GND)
Comments
kVA Size
24 kVA
Marketing part number
6444A
Manufacturing part number
597-1162-01
Phase
3
No Grounded Neutral provided in input cords
Voltage input rating
2x [3Ph. (3W+ground)] 208 Vac, 50/60 Hz, max. 34.6A per phase
Can be connected to Ph-Ph input sources in range of 190V - 220V AC nominal
Amps per PDU
120A (3 x 20A)
Outlets
42 C13
6 C19
Number of inputs
2 inputs x 60A plug, 3 ph (3W+GND)
2 inputs/plugs per PDU, or 4 total inputs/plugs for system
Input current
34.6 A max. per phase
Data center receptacle
IEC 309-3P4W-IP67
(60A, 250V, AC, 3Ph)
Outlet groups per PDU
6
Usable PDU power cord length
2 m (6.6 feet)
PDU power cords are 4 m long (13 feet), but sections are used for internal routing in the rack.
Summary:
Number of PDUs in Oracle SuperCluster T5-8: 2
Number of circuits per PDU: 2 @ 60A 3-phase 208V
Total number of circuits required: 4 @ 60A 3-phase 208V (2 per PDU)
Total number of data center receptacles required: 4 x IEC 309-3P4W-IP67
Total Amps per PDU: 120A 3-phase 208V
Total Amps for entire Oracle SuperCluster T5-8: 240A 3-phase 208V (2 PDUs @ 120A 3-phase 208V each)
Table 9  High Voltage 1 Phase PDUs
High Voltage
Single Phase (2W+GND)
Comments
kVA Size
22 kVA
Marketing part number
7100874
Manufacturing part number
7018124
Phase
1
Voltage input rating
3x [1Ph. (2W+ground)] 230 Vac, 50 Hz, max. 32A per phase
Can be connected to Ph-N input sources in range of 220V - 240V AC nominal
Amps per PDU
96A (3 inputs x 32A)
Outlets
42 C13
6 C19
Number of inputs
3 inputs x 32A plug, 1Ph (2W+ground)
3 inputs/plugs per PDU, or 6 total inputs/plugs for system
Input current
32A max. current (per input)
Data center receptacle
IEC 309-2P3W-IP44
Outlet groups per PDU
6
Usable PDU power cord length
2 m (6.6 feet)
PDU power cords are 4 m long (13 feet), but sections are used for internal routing in the rack.
Summary:
Number of PDUs in Oracle SuperCluster T5-8: 2
Number of circuits per PDU: 3 @ 32A 1-phase 230V
Total number of circuits required: 6 @ 32A 1-phase 230V (2 per PDU)
Total number of data center receptacles required: 6 x IEC 309-2P3W-IP44
Total Amps per PDU: 96A 1-phase 230V
Total Amps for entire Oracle SuperCluster T5-8: 192A 1-phase 230V (2 PDUs @ 96A 1-phase 230V each)
Table 10  High Voltage 3 Phase PDUs
High Voltage
Three Phase (4W+GND)
Comments
kVA Size
24 kVA
Marketing part number
6445A
Manufacturing part number
597-1163-01
Phase
3
Voltage input rating
2x [3Ph. (4W+ground)] 230/400 Vac, 50/60 Hz, max. 18A per phase
Can be connected to Ph-N input sources in range of 220V - 240V AC nominal
Amps per PDU
109A (6 inputs x 18.1A)
Outlets
42 C13
6 C19
Number of inputs
2 inputs x25A plug, 3 ph (4W+GND)
2 inputs/plugs per PDU, or 4 total inputs/plugs for system
Input current
18 A max. per phase
Data center receptacle
IEC 309-4P5W-IP44
(32A, 400V, AC, 3Ph)
Outlet groups per PDU
6
Usable PDU power cord length
2 m (6.6 feet)
PDU power cords are 4 m long (13 feet), but sections are used for internal routing in the rack.
Summary:
Number of PDUs in Oracle SuperCluster T5-8: 2
Number of circuits per PDU: 2 @ 25A 3-phase 230/400V
Total number of circuits required: 4 @ 25A 3-phase 230/400V (2 per PDU)
Total number of data center receptacles required: 4 x IEC 309-4P5W-IP44
Total Amps per PDU: 109A 3-phase 230/400V
Total Amps for entire Oracle SuperCluster T5-8: 218A 3-phase 230/400V (2 PDUs @ 109A 3-phase 230/400V each)