Connecting an Expansion Rack to Oracle SuperCluster T5-8
You connect an expansion rack to Oracle SuperCluster T5-8 using three Sun Datacenter InfiniBand Switch 36
switches. Oracle SuperCluster T5-8 and the Oracle Exadata Storage Expansion Half Rack or Oracle Exadata Storage Expansion Full Rack include
three Sun Datacenter InfiniBand Switch 36 switches. Two switches are used as leaf switches, and the third switch is
used as a spine switch. These switches attach to standard Quad Small Form-factor
Pluggable (QSFP) connectors at the end of the InfiniBand cables. The procedures in this
section assume the racks are adjacent to each other. If they are not, then longer cables
may be required for the connections.
InfiniBand Switch Information for Oracle SuperCluster T5-8
In Oracle SuperCluster T5-8, the switch at rack unit 1 (U1) is referred to as the
spine switch. The switches at rack unit 26 (U26) and rack unit 32 (U32)
are referred to as
leaf switches. In a single rack, the two leaf switches are
interconnected using seven connections. In addition, each leaf switch has one
connection to the spine switch. The leaf switches connect to the spine switch as
shown in the following graphic.
InfiniBand Switch Information for the Oracle Exadata Storage Expansion Rack
In the Oracle Exadata Storage Expansion Rack, the switch at rack unit 1 (U1) is referred to as the
spine switch, except for the Oracle Exadata Storage Expansion Quarter Rack which has no spine
switch. The switches at rack unit 20 (U20) and rack unit 24 (U24) are referred to as
leaf switches.
Connecting an Oracle Exadata Storage Expansion Quarter Rack to Oracle SuperCluster T5-8
These topics describe how to connect an Oracle Exadata Storage Expansion Quarter Rack to your
Oracle SuperCluster T5-8.
Note the following restrictions when connecting an Oracle Exadata Storage Expansion Quarter Rack to
Oracle SuperCluster T5-8:
-
The standard version of the Oracle Exadata Storage Expansion Quarter Rack contains two leaf switches
and no spine switch. You will typically make two connections for each leaf
switch in the Oracle Exadata Storage Expansion Quarter Rack to the leaf switches in the
Oracle SuperCluster T5-8. Each leaf switch in the Oracle SuperCluster T5-8
must therefore have four open ports for this type of connection.
-
In the Half Rack version of Oracle SuperCluster T5-8, four ports are open
on both leaf switches (ports 2A, 2B, 7B and 12A). Use the instructions in
this section to make the two connections between each leaf switch in the
Oracle Exadata Storage Expansion Quarter Rack to the leaf switches in the
Oracle SuperCluster T5-8.
-
In the Full Rack version of Oracle SuperCluster T5-8, only two ports are
open on both leaf switches (ports 2A and 2B). Therefore, if you are
connecting an Oracle Exadata Storage Expansion Quarter Rack to the Full Rack version of
Oracle SuperCluster T5-8, you must order a spine switch kit from Oracle and
install that spine switch in the Oracle Exadata Storage Expansion Quarter Rack. You would then connect
the Oracle Exadata Storage Expansion Quarter Rack to Oracle SuperCluster T5-8 using the instructions
given in Connecting an Oracle Exadata Storage Expansion Half Rack or Oracle Exadata Storage Expansion Full Rack to Oracle SuperCluster T5-8.
-
Only one Oracle Exadata Storage Expansion Quarter Rack can be connected to the Half Rack version of
Oracle SuperCluster T5-8.
The following graphic shows the cable connections from an Oracle Exadata Storage Expansion Quarter Rack to
the Half Rack version of Oracle SuperCluster T5-8. The leaf switches within each
rack maintain their existing seven connections. The leaf switches interconnect
between the racks with two links each using the ports reserved for external
connectivity.
The following graphic shows the cable connections from an Oracle Exadata Storage Expansion Quarter Rack to
two or more racks. The following racks can connect to a standard Oracle Exadata Storage Expansion Quarter Rack
(with no spine switch):
-
Half Rack version of Oracle SuperCluster T5-8
-
Oracle Exadata Storage Expansion Half Rack
-
Oracle Exadata Storage Expansion Full Rack
The racks are interconnected using a fat-tree topology. Each leaf switch in the
Oracle Exadata Storage Expansion Quarter Rack connects to the spine switches in the other Half Racks or Full
Racks with two links each. If there are more than four racks, then use one link
instead of two.
The following terms are used when referring to the two racks:
In addition, because the InfiniBand switches are physically located in different
rack units in the two racks, the following terms are used when referring to the
InfiniBand switches:
-
InfiniBand 1 (IB1) refers to the spine switch, located in U1 in
Oracle SuperCluster T5-8
-
InfiniBand 2 (IB2) refers to the first leaf switch, located in:
-
InfiniBand 3 (IB3) refers to the second leaf switch, located in:
The following table shows the cable connections for a single Oracle Exadata Storage Expansion Quarter Rack
to the Half Rack version of Oracle SuperCluster T5-8.
Table 86 Leaf Switch Connections for the First Rack in a Two-Rack System
|
|
|
R1-IB3 to Rack 2
|
R1-IB3-P2A to R2-IB3-P2A
R1-IB3-P2B to R2-IB3-P2B
R1-IB3-P7B to R2-IB2-P7B
R1-IB3-P12A to R2-IB2-P12A
|
5 meters
|
R1-IB2 to Rack 2
|
R1-IB2-P7B to R2-IB3-P7B
R1-IB2-P12A to R2-IB3-P12A
R1-IB2-P2A to R2-IB2-P2A
R1-IB2-P2B to R2-IB2-P2B
|
5 meters
|
|
Connecting an Oracle Exadata Storage Expansion Half Rack or Oracle Exadata Storage Expansion Full Rack to
Oracle SuperCluster T5-8
These topics describe how to connect an Oracle Exadata Storage Expansion Half Rack or Oracle Exadata Storage Expansion Full Rack to
your Oracle SuperCluster T5-8.
When connecting multiple racks together, remove the seven existing inter-switch
connections between each leaf switches, as well as the two connections between the
leaf switches and the spine switch. From each leaf switch, distribute eight
connections over the spine switches in all racks. In multi-rack environments, the
leaf switches inside a rack are no longer directly interconnected, as shown in the
following graphic.
As shown in the preceding graphic, each leaf switch in rack 1 connects to the
following switches:
The spine switch in rack 1 connects to the following switches:
The following terms are used when referring to the two racks:
In addition, because the InfiniBand switches are physically located in different
rack units in the two racks, the following terms are used when referring to the
InfiniBand switches:
-
InfiniBand 1 (IB1) refers to the spine switch, located in U1 in both
racks
-
InfiniBand 2 (IB2) refers to the first leaf switch, located in:
-
InfiniBand 3 (IB3) refers to the second leaf switch, located in:
The following sections provide information for connecting Oracle Exadata Storage Expansion Half Rack or
Oracle Exadata Storage Expansion Full Rack to your Oracle SuperCluster T5-8:
Two-Rack Cabling
The following table shows the cable connections for the first spine switch
(R1-IB1) when cabling two racks together.
Table 87 Leaf Switch Connections for the First Rack in a Two-Rack System
|
|
|
R1-IB3 within Rack 1
|
R1-IB3-P8A to R1-IB1-P3A
R1-IB3-P8B to R1-IB1-P4A
R1-IB3-P9A to R1-IB1-P5A
R1-IB3-P9B to R1-IB1-P6A
|
5 meters
|
R1-IB3 to Rack 2
|
R1-IB3-P10A to R2-IB1-P7A
R1-IB3-P10B to R2-IB1-P8A
R1-IB3-P11A to R2-IB1-P9A
R1-IB3-P11B to R2-IB1-P10A
|
5 meters
|
R1-IB2 within Rack 1
|
R1-IB2-P8A to R1-IB1-P3B
R1-IB2-P8B to R1-IB1-P4B
R1-IB2-P9A to R1-IB1-P5B
R1-IB2-P9B to R1-IB1-P6B
|
5 meters
|
R1-IB2 to Rack 2
|
R1-IB2-P10A to R2-IB1-P7B
R1-IB2-P10B to R2-IB1-P8B
R1-IB2-P11A to R2-IB1-P9B
R1-IB2-P11B to R2-IB1-P10B
|
5 meters
|
|
The following table shows the cable connections for the second spine switch
(R2-IB1) when cabling two racks together.
Table 88 Leaf Switch Connections for the Second Rack in a Two-Rack System
|
|
|
R2-IB3 within Rack 2
|
R2-IB3-P8A to R2-IB1-P3A
R2-IB3-P8B to R2-IB1-P4A
R2-IB3-P9A to R2-IB1-P5A
R2-IB3-P9B to R2-IB1-P6A
|
5 meters
|
R2-IB3 to Rack 1
|
R2-IB3-P10A to R1-IB1-P7A
R2-IB3-P10B to R1-IB1-P8A
R2-IB3-P11A to R1-IB1-P9A
R2-IB3-P11B to R1-IB1-P10A
|
5 meters
|
R2-IB2 within Rack 2
|
R2-IB2-P8A to R2-IB1-P3B
R2-IB2-P8B to R2-IB1-P4B
R2-IB2-P9A to R2-IB1-P5B
R2-IB2-P9B to R2-IB1-P6B
|
5 meters
|
R2-IB2 to Rack 1
|
R2-IB2-P10A to R1-IB1-P7B
R2-IB2-P10B to R1-IB1-P8B
R2-IB2-P11A to R1-IB1-P9B
R2-IB2-P11B to R1-IB1-P10B
|
5 meters
|
|
Three-Rack Cabling
The following table shows the cable connections for the first spine switch
(R1-IB1) when cabling three full racks together.
Table 89 Leaf Switch Connections for the First Rack in a Three-Rack System
|
|
|
R1-IB3 within Rack 1
|
R1-IB3-P8A to R1-IB1-P3A
R1-IB3-P8B to R1-IB1-P4A
R1-IB3-P9A to R1-IB1-P5A
|
5 meters
|
R1-IB3 to Rack 2
|
R1-IB3-P9B to R2-IB1-P6A
R1-IB3-P10A to R2-IB1-P7A
R1-IB3-P10B to R2-IB1-P8A
|
5 meters
|
R1-IB3 to Rack 3
|
R1-IB3-P11A to R3-IB1-P9A
R1-IB3-P11B to R3-IB1-P10A
|
5 meters
|
R1-IB2 within Rack 1
|
R1-IB2-P8A to R1-IB1-P3B
R1-IB2-P8B to R1-IB1-P4B
R1-IB2-P9A to R1-IB1-P5B
|
5 meters
|
R1-IB2 to Rack 2
|
R1-IB2-P9B to R2-IB1-P6B
R1-IB2-P10A to R2-IB1-P7B
R1-IB2-P10B to R2-IB1-P8B
|
5 meters
|
R1-IB2 to Rack 3
|
R1-IB2-P11A to R3-IB1-P9B
R1-IB2-P11B to R3-IB1-P10B
|
5 meters
|
|
The following table shows the cable connections for the second spine switch
(R2-IB1) when cabling three racks together.
Table 90 Leaf Switch Connections for the Second Rack in a Three-Rack System
|
|
|
R2-IB3 within Rack 2
|
R2-IB3-P8A to R2-IB1-P3A
R2-IB3-P8B to R2-IB1-P4A
R2-IB3-P9A to R2-IB1-P5A
|
5 meters
|
R2-IB3 to Rack 1
|
R2-IB3-P11A to R1-IB1-P9A
R2-IB3-P11B to R1-IB1-P10A
|
5 meters
|
R2-IB3 to Rack 3
|
R2-IB3-P9B to R3-IB1-P6A
R2-IB3-P10A to R3-IB1-P7A
R2-IB3-P10B to R3-IB1-P8A
|
5 meters
|
R2-IB2 within Rack 2
|
R2-IB2-P8A to R2-IB1-P3B
R2-IB2-P8B to R2-IB1-P4B
R2-IB2-P9A to R2-IB1-P5B
|
5 meters
|
R2-IB2 to Rack 1
|
R2-IB2-P11A to R1-IB1-P9B
R2-IB2-P11B to R1-IB1-P10B
|
5 meters
|
R2-IB2 to Rack 3
|
R2-IB2-P9B to R3-IB1-P6B
R2-IB2-P10A to R3-IB1-P7B
R2-IB2-P10B to R3-IB1-P8B
|
5 meters
|
|
The following table shows the cable connections for the third spine switch
(R3-IB1) when cabling three full racks together.
Table 91 Leaf Switch Connections for the Third Rack in a Three-Rack System
|
|
|
R3-IB3 within Rack 3
|
R3-IB3-P8A to R3-IB1-P3A
R3-IB3-P8B to R3-IB1-P4A
R3-IB3-P9A to R3-IB1-P5A
|
5 meters
|
R3-IB3 to Rack 1
|
R3-IB3-P9B to R1-IB1-P6A
R3-IB3-P10A to R1-IB1-P7A
R3-IB3-P10B to R1-IB1-P8A
|
5 meters
|
R3-IB3 to Rack 2
|
R3-IB3-P11A to R2-IB1-P9A
R3-IB3-P11B to R2-IB1-P10A
|
5 meters
|
R3-IB2 within Rack 3
|
R3-IB2-P8A to R3-IB1-P3B
R3-IB2-P8B to R3-IB1-P4B
R3-IB2-P9A to R3-IB1-P5B
|
5 meters
|
R3-IB2 to Rack 1
|
R3-IB2-P9B to R1-IB1-P6B
R3-IB2-P10A to R1-IB1-P7B
R3-IB2-P10B to R1-IB1-P8B
|
5 meters
|
R3-IB2 to Rack 2
|
R3-IB2-P11A to R2-IB1-P9B
R3-IB2-P11B to R2-IB1-P10B
|
5 meters
|
|
Four-Rack Cabling
The following table shows the cable connections for the first spine switch
(R1-IB1) when cabling four full racks together.
Table 92 Leaf Switch Connections for the First Rack in a Four-Rack System
|
|
|
R1-IB3 within Rack 1
|
R1-IB3-P8A to R1-IB1-P3A
R1-IB3-P8B to R1-IB1-P4A
|
5 meters
|
R1-IB3 to Rack 2
|
R1-IB3-P9A to R2-IB1-P5A
R1-IB3-P9B to R2-IB1-P6A
|
5 meters
|
R1-IB3 to Rack 3
|
R1-IB3-P10A to R3-IB1-P7A
R1-IB3-P10B to R3-IB1-P8A
|
5 meters
|
R1-IB3 to Rack 4
|
R1-IB3-P11A to R4-IB1-P9A
R1-IB3-P11B to R4-IB1-P10A
|
10 meters
|
R1-IB2 within Rack 1
|
R1-IB2-P8A to R1-IB1-P3B
R1-IB2-P8B to R1-IB1-P4B
|
5 meters
|
R1-IB2 to Rack 2
|
R1-IB2-P9A to R2-IB1-P5B
R1-IB2-P9B to R2-IB1-P6B
|
5 meters
|
R1-IB2 to Rack 3
|
R1-IB2-P10A to R3-IB1-P7B
R1-IB2-P10B to R3-IB1-P8B
|
5 meters
|
R1-IB2 to Rack 4
|
R1-IB2-P11A to R4-IB1-P9B
R1-IB2-P11B to R4-IB1-P10B
|
10 meters
|
|
The following table shows the cable connections for the second spine switch
(R2-IB1) when cabling four full racks together.
Table 93 Leaf Switch Connections for the Second Rack in a Four-Rack System
|
|
|
R2-IB3 within Rack 2
|
R2-IB3-P8A to R2-IB1-P3A
R2-IB3-P8B to R2-IB1-P4A
|
5 meters
|
R2-IB3 to Rack 1
|
R2-IB3-P11A to R1-IB1-P9A
R2-IB3-P11B to R1-IB1-P10A
|
5 meters
|
R2-IB3 to Rack 3
|
R2-IB3-P9A to R3-IB1-P5A
R2-IB3-P9B to R3-IB1-P6A
|
5 meters
|
R2-IB3 to Rack 4
|
R2-IB3-P10A to R4-IB1-P7A
R2-IB3-P10B to R4-IB1-P8A
|
5 meters
|
R2-IB2 within Rack 2
|
R2-IB2-P8A to R2-IB1-P3B
R2-IB2-P8B to R2-IB1-P4B
|
5 meters
|
R2-IB2 to Rack 1
|
R2-IB2-P11A to R1-IB1-P9B
R2-IB2-P11B to R1-IB1-P10B
|
5 meters
|
R2-IB2 to Rack 3
|
R2-IB2-P9A to R3-IB1-P5B
R2-IB2-P9B to R3-IB1-P6B
|
5 meters
|
R2-IB2 to Rack 4
|
R2-IB2-P10A to R4-IB1-P7B
R2-IB2-P10B to R4-IB1-P8B
|
5 meters
|
|
The following table shows the cable connections for the third spine switch
(R3-IB1) when cabling four full racks together.
Table 94 Leaf Switch Connections for the Third Rack in a Four-Rack System
|
|
|
R3-IB3 within Rack 3
|
R3-IB3-P8A to R3-IB1-P3A
R3-IB3-P8B to R3-IB1-P4A
|
5 meters
|
R3-IB3 to Rack 1
|
R3-IB3-P10A to R1-IB1-P7A
R3-IB3-P10B to R1-IB1-P8A
|
5 meters
|
R3-IB3 to Rack 2
|
R3-IB3-P11A to R2-IB1-P9A
R3-IB3-P11B to R2-IB1-P10A
|
5 meters
|
R3-IB3 to Rack 4
|
R3-IB3-P9A to R4-IB1-P5A
R3-IB3-P9B to R4-IB1-P6A
|
5 meters
|
R3-IB2 within Rack 3
|
R3-IB2-P8A to R3-IB1-P3B
R3-IB2-P8B to R3-IB1-P4B
|
5 meters
|
R3-IB2 to Rack 1
|
R3-IB2-P10A to R1-IB1-P7B
R3-IB2-P10B to R1-IB1-P8B
|
5 meters
|
R3-IB2 to Rack 2
|
R3-IB2-P11A to R2-IB1-P9B
R3-IB2-P11B to R2-IB1-P10B
|
5 meters
|
R3-IB2 to Rack 4
|
R3-IB2-P9A to R4-IB1-P5B
R3-IB2-P9B to R4-IB1-P6B
|
5 meters
|
|
The following table shows the cable connections for the fourth spine switch
(R4-IB1) when cabling four full racks together.
Table 95 Leaf Switch Connections for the Fourth Rack in a Four-Rack System
|
|
|
R4-IB3 within Rack 4
|
R4-IB3-P8A to R4-IB1-P3A
R4-IB3-P8B to R4-IB1-P4A
|
5 meters
|
R4-IB3 to Rack 1
|
R4-IB3-P9A to R1-IB1-P5A
R4-IB3-P9B to R1-IB1-P6A
|
10 meters
|
R4-IB3 to Rack 2
|
R4-IB3-P10A to R2-IB1-P7A
R4-IB3-P10B to R2-IB1-P8A
|
5 meters
|
R4-IB3 to Rack 3
|
R4-IB3-P11A to R3-IB1-P9A
R4-IB3-P11B to R3-IB1-P10A
|
5 meters
|
R4-IB2 within Rack 4
|
R4-IB2-P8A to R4-IB1-P3B
R4-IB2-P8B to R4-IB1-P4B
|
5 meters
|
R4-IB2 to Rack 1
|
R4-IB2-P9A to R1-IB1-P5B
R4-IB2-P9B to R1-IB1-P6B
|
10 meters
|
R4-IB2 to Rack 2
|
R4-IB2-P10A to R2-IB1-P7B
R4-IB2-P10B to R2-IB1-P8B
|
5 meters
|
R4-IB2 to Rack 3
|
R4-IB2-P11A to R3-IB1-P9B
R4-IB2-P11B to R3-IB1-P10B
|
5 meters
|
|
Five-Rack Cabling
The following table shows the cable connections for the first spine switch
(R1-IB1) when cabling five full racks together.
Table 96 Leaf Switch Connections for the First Rack in a Five-Rack System
|
|
|
R1 IB3 within Rack 1
|
R1-IB3-P8A to R1-IB1-P3A
R1-IB3-P8B to R1-IB1-P4A
|
3 meters
|
R1 IB3 to Rack 2
|
R1-IB3-P9A to R2-IB1-P5A
R1-IB3-P9B to R2-IB1-P6A
|
5 meters
|
R1 IB3 to Rack 3
|
R1-IB3-P10A to R3-IB1-P7A
R1-IB3-P10B to R3-IB1-P8A
|
5 meters
|
R1 IB3 to Rack 4
|
R1-IB3-P11A to R4-IB1-P9A
|
10 meters
|
R1 IB3 to Rack 5
|
R1-IB3-P11B to R5-IB1-P10A
|
10 meters
|
R1 IB2 within Rack 1
|
R1-IB2-P8A to R1-IB1-P3B
R1-IB2-P8B to R1-IB1-P4B
|
3 meters
|
R1 IB2 to Rack 2
|
R1-IB2-P9A to R2-IB1-P5B
R1-IB2-P9B to R2-IB1-P6B
|
3 meters
|
R1 IB2 to Rack 3
|
R1-IB2-P10A to R3-IB1-P7B
R1-IB2-P10B to R3-IB1-P8B
|
5 meters
|
R1 IB2 to Rack 4
|
R1-IB2-P11A to R4-IB1-P9B
|
10 meters
|
R1 IB2 to Rack 5
|
R1-IB2-P11B to R5-IB1-P10B
|
10 meters
|
|
The following table shows the cable connections for the second spine switch
(R2-IB1) when cabling five full racks together.
Table 97 Leaf Switch Connections for the Second Rack in a Five-Rack System
|
|
|
R2 IB3 within Rack 2
|
R2-IB3-P8A to R2-IB1-P3A
R2-IB3-P8B to R2-IB1-P4A
|
3 meters
|
R2 IB3 to Rack 1
|
R2-IB3-P11B to R1-IB1-P10A
|
5 meters
|
R2 IB3 to Rack 3
|
R2-IB3-P9A to R3-IB1-P5A
R2-IB3-P9B to R3-IB1-P6A
|
5 meters
|
R2 IB3 to Rack 4
|
R2-IB3-P10A to R4-IB1-P7A
R2-IB3-P10B to R4-IB1-P8A
|
5 meters
|
R2 IB3 to Rack 5
|
R2-IB3-P11A to R5-IB1-P9A
|
10 meters
|
R2 IB2 within Rack 2
|
R2-IB2-P8A to R2-IB1-P3B
R2-IB2-P8B to R2-IB1-P4B
|
3 meters
|
R2 IB2 to Rack 1
|
R2-IB2-P11B to R1-IB1-P10B
|
5 meters
|
R2 IB2 to Rack 3
|
R2-IB2-P9A to R3-IB1-P5B
R2-IB2-P9B to R3-IB1-P6B
|
5 meters
|
R2 IB2 to Rack 4
|
R2-IB2-P10A to R4-IB1-P7B
R2-IB2-P10B to R4-IB1-P8B
|
5 meters
|
R2 IB2 to Rack 5
|
R2-IB2-P11A to R5-IB1-P9B
|
10 meters
|
|
The following table shows the cable connections for the third spine switch
(R3-IB1) when cabling five full racks together.
Table 98 Leaf Switch Connections for the Third Rack in a Five-Rack System
|
|
|
R3 IB3 within Rack 3
|
R3-IB3-P8A to R3-IB1-P3A
R3-IB3-P8B to R3-IB1-P4A
|
3 meters
|
R3 IB3 to Rack 1
|
R3-IB3-P11A to R1-IB1-P9A
|
5 meters
|
R3 IB3 to Rack 2
|
R3-IB3-P11B to R2-IB1-P10A
|
5 meters
|
R3 IB3 to Rack 4
|
R3-IB3-P9A to R4-IB1-P5A
R3-IB3-P9B to R4-IB1-P6A
|
5 meters
|
R3 IB3 to Rack 5
|
R3-IB3-P10A to R5-IB1-P7A
R3-IB3-P10B to R5-IB1-P8A
|
5 meters
|
R3 IB2 within Rack 3
|
R3-IB2-P8A to R3-IB1-P3B
R3-IB2-P8B to R3-IB1-P4B
|
3 meters
|
R3 IB2 to Rack 1
|
R3-IB2-P11A to R1-IB1-P9B
|
5 meters
|
R3 IB2 to Rack 2
|
R3-IB2-P11B to R2-IB1-P10B
|
5 meters
|
R3 IB2 to Rack 4
|
R3-IB2-P9A to R4-IB1-P5B
R3-IB2-P9B to R4-IB1-P6B
|
5 meters
|
R3 IB2 to Rack 5
|
R3-IB2-P10A to R5-IB1-P7B
R3-IB2-P10B to R5-IB1-P8B
|
5 meters
|
|
The following table shows the cable connections for the fourth spine switch
(R4-IB1) when cabling five full racks together.
Table 99 Leaf Switch Connections for the Fourth Rack in a Five-Rack System
|
|
|
R4 IB3 within Rack 4
|
R4-IB3-P8A to R4-IB1-P3A
R4-IB3-P8B to R4-IB1-P4A
|
3 meters
|
R4 IB3 to Rack 1
|
R4-IB3-P10A to R1-IB1-P7A
R4-IB3-P10B to R1-IB1-P8A
|
10 meters
|
R4 IB3 to Rack 2
|
R4-IB3-P11A to R2-IB1-P9A
|
5 meters
|
R4 IB3 to Rack 3
|
R4-IB3-P11B to R3-IB1-P10A
|
5 meters
|
R4 IB3 to Rack 5
|
R4-IB3-P9A to R5-IB1-P5A
R4-IB3-P9B to R5-IB1-P6A
|
5 meters
|
R4 IB2 within Rack 4
|
R4-IB2-P8A to R4-IB1-P3B
R4-IB2-P8B to R4-IB1-P4B
|
3 meters
|
R4 IB2 to Rack 1
|
R4-IB2-P10A to R1-IB1-P7B
R4-IB2-P10B to R1-IB1-P8B
|
10 meters
|
R4 IB2 to Rack 2
|
R4-IB2-P11A to R2-IB1-P9B
|
5 meters
|
R4 IB2 to Rack 3
|
R4-IB2-P11B to R3-IB1-P10B
|
5 meters
|
R4 IB2 to Rack 5
|
R4-IB2-P9A to R5-IB1-P5B
R4-IB2-P9B to R5-IB1-P6B
|
5 meters
|
|
The following table shows the cable connections for the fifth spine switch
(R5-IB1) when cabling five full racks together.
Table 100 Leaf Switch Connections for the Fifth Rack in a Five-Rack System
|
|
|
R5 IB3 within Rack 5
|
R5-IB3-P8A to R5-IB1-P3A
R5-IB3-P8B to R5-IB1-P4A
|
3 meters
|
R5 IB3 to Rack 1
|
R5-IB3-P9A to R1-IB1-P5A
R5-IB3-P9B to R1-IB1-P6A
|
10 meters
|
R5 IB3 to Rack 2
|
R5-IB3-P10A to R2-IB1-P7A
R5-IB3-P10B to R2-IB1-P8A
|
10 meters
|
R5 IB3 to Rack 3
|
R5-IB3-P11A to R3-IB1-P9A
|
5 meters
|
R5 IB3 to Rack 4
|
R5-IB3-P11B to R4-IB1-P10A
|
5 meters
|
R5 IB2 within Rack 5
|
R5-IB2-P8A to R5-IB1-P3B
R5-IB2-P8B to R5-IB1-P4B
|
3 meters
|
R5 IB2 to Rack 1
|
R5-IB2-P9A to R1-IB1-P5B
R5-IB2-P9B to R1-IB1-P6B
|
10 meters
|
R5 IB2 to Rack 2
|
R5-IB2-P10A to R2-IB1-P7B
R5-IB2-P10B to R2-IB1-P8B
|
10 meters
|
R5 IB2 to Rack 3
|
R5-IB2-P11A to R3-IB1-P9B
|
5 meters
|
R5 IB2 to Rack 4
|
R5-IB2-P11B to R4-IB1-P10B
|
5 meters
|
|
Six-Rack Cabling
The following table shows the cable connections for the first spine switch
(R1-IB1) when cabling six full racks together.
Table 101 Leaf Switch Connections for the First Rack in a Six-Rack System
|
|
|
R1 IB3 within Rack 1
|
R1-IB3-P8A to R1-IB1-P3A
R1-IB3-P8B to R1-IB1-P4A
|
3 meters
|
R1 IB3 to Rack 2
|
R1-IB3-P9A to R2-IB1-P5A
R1-IB3-P9B to R2-IB1-P6A
|
5 meters
|
R1 IB3 to Rack 3
|
R1-IB3-P10A to R3-IB1-P7A
|
5 meters
|
R1 IB3 to Rack 4
|
R1-IB3-P10B to R4-IB1-P8A
|
10 meters
|
R1 IB3 to Rack 5
|
R1-IB3-P11A to R5-IB1-P9A
|
10 meters
|
R1 IB3 to Rack 6
|
R1-IB3-P11B to R6-IB1-P10A
|
10 meters
|
R1 IB2 within Rack 1
|
R1-IB2-P8A to R1-IB1-P3B
R1-IB2-P8B to R1-IB1-P4B
|
3 meters
|
R1 IB2 to Rack 2
|
R1-IB2-P9A to R2-IB1-P5B
R1-IB2-P9B to R2-IB1-P6B
|
5 meters
|
R1 IB2 to Rack 3
|
R1-IB2-P10A to R3-IB1-P7B
|
5 meters
|
R1 IB2 to Rack 4
|
R1-IB2-P10B to R4-IB1-P8B
|
10 meters
|
R1 IB2 to Rack 5
|
R1-IB2-P11A to R5-IB1-P9B
|
10 meters
|
R1 IB2 to Rack 6
|
R1-IB2-P11B to R6-IB1-P10B
|
10 meters
|
|
The following table shows the cable connections for the second spine switch
(R2-IB1) when cabling six full racks together.
Table 102 Leaf Switch Connections for the Second Rack in a Six-Rack System
|
|
|
R2 IB3 within Rack 2
|
R2-IB3-P8A to R2-IB1-P3A
R2-IB3-P8B to R2-IB1-P4A
|
3 meters
|
R2 IB3 to Rack 1
|
R2-IB3-P11B to R1-IB1-P10A
|
5 meters
|
R2 IB3 to Rack 3
|
R2-IB3-P9A to R3-IB1-P5A
R2-IB3-P9B to R3-IB1-P6A
|
5 meters
|
R2 IB3 to Rack 4
|
R2-IB3-P10A to R4-IB1-P7A
|
5 meters
|
R2 IB3 to Rack 5
|
R2-IB3-P10B to R5-IB1-P8A
|
10 meters
|
R2 IB3 to Rack 6
|
R2-IB3-P11Ato R6-IB1-P9A
|
10 meters
|
R2 IB2 within Rack 2
|
R2-IB2-P8A to R2-IB1-P3B
R2-IB2-P8B to R2-IB1-P4B
|
3 meters
|
R2 IB2 to Rack 1
|
R2-IB2-P11B to R1-IB1-P10B
|
5 meters
|
R2 IB2 to Rack 3
|
R2-IB2-P9A to R3-IB1-P5B
R2-IB2-P9B to R3-IB1-P6B
|
5 meters
|
R2 IB2 to Rack 4
|
R2-IB2-P10A to R4-IB1-P7B
|
5 meters
|
R2 IB2 to Rack 5
|
R2-IB2-P10B to R5-IB1-P8B
|
10 meters
|
R2 IB2 to Rack 6
|
R2-IB2-P11Ato R6-IB1-P9B
|
10 meters
|
|
The following table shows the cable connections for the third spine switch
(R3-IB1) when cabling six full racks together.
Table 103 Leaf Switch Connections for the Third Rack in a Six-Rack System
|
|
|
R3 IB3 within Rack 3
|
R3-IB3-P8A to R3-IB1-P3A
R3-IB3-P8B to R3-IB1-P4A
|
3 meters
|
R3 IB3 to Rack 1
|
R3-IB3-P11A to R1-IB1-P9A
|
5 meters
|
R3 IB3 to Rack 2
|
R3-IB3-P11B to R2-IB1-P10A
|
5 meters
|
R3 IB3 to Rack 4
|
R3-IB3-P9A to R4-IB1-P5A
R3-IB3-P9B to R4-IB1-P6A
|
5 meters
|
R3 IB3 to Rack 5
|
R3-IB3-P10A to R5-IB1-P7A
|
5 meters
|
R3 IB3 to Rack 6
|
R3-IB3-P10B to R6-IB1-P8A
|
5 meters
|
R3 IB2 within Rack 3
|
R3-IB2-P8A to R3-IB1-P3B
R3-IB2-P8B to R3-IB1-P4B
|
3 meters
|
R3 IB2 to Rack 1
|
R3-IB2-P11A to R1-IB1-P9B
|
5 meters
|
R3 IB2 to Rack 2
|
R3-IB2-P11B to R2-IB1-P10B
|
5 meters
|
R3 IB2 to Rack 4
|
R3-IB2-P9A to R4-IB1-P5B
R3-IB2-P9B to R4-IB1-P6B
|
5 meters
|
R3 IB2 to Rack 5
|
R3-IB2-P10A to R5-IB1-P7B
|
5 meters
|
R3 IB2 to Rack 6
|
R3-IB2-P10B to R6-IB1-P8B
|
5 meters
|
|
The following table shows the cable connections for the fourth spine switch
(R4-IB1) when cabling six full racks together.
Table 104 Leaf Switch Connections for the Fourth Rack in a Six-Rack System
|
|
|
R4 IB3 within Rack 4
|
R4-IB3-P8A to R4-IB1-P3A
R4-IB3-P8B to R4-IB1-P4A
|
3 meters
|
R4 IB3 to Rack 1
|
R4-IB3-P10B to R1-IB1-P8A
|
10 meters
|
R4 IB3 to Rack 2
|
R4-IB3-P11A to R2-IB1-P9A
|
5 meters
|
R4 IB3 to Rack 3
|
R4-IB3-P11B to R3-IB1-P10A
|
5 meters
|
R4 IB3 to Rack 5
|
R4-IB3-P9A to R5-IB1-P5A
R4-IB3-P9B to R5-IB1-P6A
|
5 meters
|
R4 IB3 to Rack 6
|
R4-IB3-P10A to R6-IB1-P7A
|
5 meters
|
R4 IB2 within Rack 4
|
R4-IB2-P8A to R4-IB1-P3B
R4-IB2-P8B to R4-IB1-P4B
|
3 meters
|
R4 IB2 to Rack 1
|
R4-IB2-P10B to R1-IB1-P8B
|
10 meters
|
R4 IB2 to Rack 2
|
R4-IB2-P11A to R2-IB1-P9B
|
5 meters
|
R4 IB2 to Rack 3
|
R4-IB2-P11B to R3-IB1-P10B
|
5 meters
|
R4 IB2 to Rack 5
|
R4-IB2-P9A to R5-IB1-P5B
R4-IB2-P9B to R5-IB1-P6B
|
5 meters
|
R4 IB2 to Rack 6
|
R4-IB2-P10A to R6-IB1-P7B
|
5 meters
|
|
The following table shows the cable connections for the fifth spine switch
(R5-IB1) when cabling six full racks together.
Table 105 Leaf Switch Connections for the Fifth Rack in a Six-Rack System
|
|
|
R5 IB3 within Rack 5
|
R5-IB3-P8A to R5-IB1-P3A
R5-IB3-P8B to R5-IB1-P4A
|
3 meters
|
R5 IB3 to Rack 1
|
R5-IB3-P10A to R1-IB1-P7A
|
10 meters
|
R5 IB3 to Rack 2
|
R5-IB3-P10B to R2-IB1-P8A
|
10 meters
|
R5 IB3 to Rack 3
|
R5-IB3-P11A to R3-IB1-P9A
|
5 meters
|
R5 IB3 to Rack 4
|
R5-IB3-P11B to R4-IB1-P10A
|
5 meters
|
R5 IB3 to Rack 6
|
R5-IB3-P9A to R6-IB1-P5A
R5-IB3-P9B to R6-IB1-P6A
|
5 meters
|
R5 IB2 within Rack 5
|
R5-IB2-P8A to R5-IB1-P3B
R5-IB2-P8B to R5-IB1-P4B
|
3 meters
|
R5 IB2 to Rack 1
|
R5-IB2-P10A to R1-IB1-P7B
|
10 meters
|
R5 IB2 to Rack 2
|
R5-IB2-P10B to R2-IB1-P8B
|
10 meters
|
R5 IB2 to Rack 3
|
R5-IB2-P11A to R3-IB1-P9B
|
5 meters
|
R5 IB2 to Rack 4
|
R5-IB2-P11B to R4-IB1-P10B
|
5 meters
|
R5 IB2 to Rack 6
|
R5-IB2-P9A to R6-IB1-P5B
R5-IB2-P9B to R6-IB1-P6B
|
5 meters
|
|
The following table shows the cable connections for the sixth spine switch
(R6-IB1) when cabling six full racks together.
Table 106 Leaf Switch Connections for the Sixth Rack in a Six-Rack System
|
|
|
R6 IB3 within Rack 6
|
R6-IB3-P8A to R6-IB1-P3A
R6-IB3-P8B to R6-IB1-P4A
|
3 meters
|
R6 IB3 to Rack 1
|
R6-IB3-P9A to R1-IB1-P5A
R6-IB3-P9B to R1-IB1-P6A
|
10 meters
|
R6 IB3 to Rack 2
|
R6-IB3-P10A to R2-IB1-P7A
|
10 meters
|
R6 IB3 to Rack 3
|
R6-IB3-P10B to R3-IB1-P8A
|
5 meters
|
R6 IB3 to Rack 4
|
R6-IB3-P11A to R4-IB1-P9A
|
5 meters
|
R6 IB3 to Rack 5
|
R6-IB3-P11B to R5-IB1-P10A
|
5 meters
|
R6 IB2 within Rack 6
|
R6-IB2-P8A to R6-IB1-P3B
R6-IB2-P8B to R6-IB1-P4B
|
3 meters
|
R6 IB2 to Rack 2
|
R6-IB2-P10A to R2-IB1-P7B
|
10 meters
|
R6 IB2 to Rack 1
|
R6-IB2-P9A to R1-IB1-P5B
R6-IB2-P9B to R1-IB1-P6B
|
10 meters
|
R6 IB2 to Rack 3
|
R6-IB2-P10B to R3-IB1-P8B
|
5 meters
|
R6 IB2 to Rack 4
|
R6-IB2-P11A to R4-IB1-P9B
|
5 meters
|
R6 IB2 to Rack 5
|
R6-IB2-P11B to R5-IB1-P10B
|
5 meters
|
|
Seven-Rack Cabling
The following table shows the cable connections for the first spine switch
(R1-IB1) when cabling seven full racks together.
Table 107 Leaf Switch Connections for the First Rack in a Seven-Rack System
|
|
|
R1 IB3 within Rack 1
|
R1-IB3-P8A to R1-IB1-P3A
R1-IB3-P8B to R1-IB1-P4A
|
3 meters
|
R1 IB3 to Rack 2
|
R1-IB3-P9A to R2-IB1-P5A
|
5 meters
|
R1 IB3 to Rack 3
|
R1-IB3-P9B to R3-IB1-P6A
|
5 meters
|
R1 IB3 to Rack 4
|
R1-IB3-P10A to R4-IB1-P7A
|
10 meters
|
R1 IB3 to Rack 5
|
R1-IB3-P10B to R5-IB1-P8A
|
10 meters
|
R1 IB3 to Rack 6
|
R1-IB3-P11A to R6-IB1-P9A
|
10 meters
|
R1 IB3 to Rack 7
|
R1-IB3-P11B to R7-IB1-P10A
|
10 meters
|
R1 IB2 within Rack 1
|
R1-IB2-P8A to R1-IB1-P3B
R1-IB2-P8B to R1-IB1-P4B
|
3 meters
|
R1 IB2 to Rack 2
|
R1-IB2-P9A to R2-IB1-P5B
|
5 meters
|
R1 IB2 to Rack 3
|
R1-IB2-P9B to R3-IB1-P6B
|
5 meters
|
R1 IB2 to Rack 4
|
R1-IB2-P10A to R4-IB1-P7B
|
10 meters
|
R1 IB2 to Rack 5
|
R1-IB2-P10B to R5-IB1-P8B
|
10 meters
|
R1 IB2 to Rack 6
|
R1-IB2-P11A to R6-IB1-P9B
|
10 meters
|
R1 IB2 to Rack 7
|
R1-IB2-P11B to R7-IB1-P10B
|
10 meters
|
|
The following table shows the cable connections for the second spine switch
(R2-IB1) when cabling seven full racks together.
Table 108 Leaf Switch Connections for the Second Rack in a Seven-Rack System
|
|
|
R2 IB3 within Rack 2
|
R2-IB3-P8A to R2-IB1-P3A
R2-IB3-P8B to R2-IB1-P4A
|
3 meters
|
R2 IB3 to Rack 1
|
R2-IB3-P11B to R1-IB1-P10A
|
5 meters
|
R2 IB3 to Rack 3
|
R2-IB3-P9A to R3-IB1-P5A
|
5 meters
|
R2 IB3 to Rack 4
|
R2-IB3-P9B to R4-IB1-P6A
|
5 meters
|
R2 IB3 to Rack 5
|
R2-IB3-P10A to R5-IB1-P7A
|
10 meters
|
R2 IB3 to Rack 6
|
R2-IB3-P10B to R6-IB1-P8A
|
10 meters
|
R2 IB3 to Rack 7
|
R2-IB3-P11A to R7-IB1-P9A
|
10 meters
|
R2 IB2 within Rack 2
|
R2-IB2-P8A to R2-IB1-P3B
R2-IB2-P8B to R2-IB1-P4B
|
3 meters
|
R2 IB2 to Rack 1
|
R2-IB2-P11B to R1-IB1-P10B
|
5 meters
|
R2 IB2 to Rack 3
|
R2-IB2-P9A to R3-IB1-P5B
|
5 meters
|
R2 IB2 to Rack 4
|
R2-IB2-P9B to R4-IB1-P6B
|
5 meters
|
R2 IB2 to Rack 5
|
R2-IB2-P10A to R5-IB1-P7B
|
10 meters
|
R2 IB2 to Rack 6
|
R2-IB2-P10Bto R6-IB1-P8B
|
10 meters
|
R2 IB2 to Rack 7
|
R2-IB2-P11A to R7-IB1-P9B
|
10 meters
|
|
The following table shows the cable connections for the third spine switch
(R3-IB1) when cabling seven full racks together.
Table 109 Leaf Switch Connections for the Third Rack in a Seven-Rack System
|
|
|
R3 IB3 within Rack 3
|
R3-IB3-P8A to R3-IB1-P3A
R3-IB3-P8B to R3-IB1-P4A
|
3 meters
|
R3 IB3 to Rack 1
|
R3-IB3-P11A to R1-IB1-P9A
|
5 meters
|
R3 IB3 to Rack 2
|
R3-IB3-P11B to R2-IB1-P10A
|
5 meters
|
R3 IB3 to Rack 4
|
R3-IB3-P9A to R4-IB1-P5A
|
5 meters
|
R3 IB3 to Rack 5
|
R3-IB3-P9B to R5-IB1-P6A
|
5 meters
|
R3 IB3 to Rack 6
|
R3-IB3-P10A to R6-IB1-P7A
|
10 meters
|
R3 IB3 to Rack 7
|
R3-IB3-P10B to R7-IB1-P8A
|
10 meters
|
R3 IB2 within Rack 3
|
R3-IB2-P8A to R3-IB1-P3B
R3-IB2-P8B to R3-IB1-P4B
|
3 meters
|
R3 IB2 to Rack 1
|
R3-IB2-P11A to R1-IB1-P9B
|
5 meters
|
R3 IB2 to Rack 2
|
R3-IB2-P11B to R2-IB1-P10B
|
5 meters
|
R3 IB2 to Rack 4
|
R3-IB2-P9A to R4-IB1-P5B
|
5 meters
|
R3 IB2 to Rack 5
|
R3-IB2-P9B to R5-IB1-P6B
|
5 meters
|
R3 IB2 to Rack 6
|
R3-IB2-P10A to R6-IB1-P7B
|
10 meters
|
R3 IB2 to Rack 7
|
R3-IB2-P10B to R7-IB1-P8B
|
10 meters
|
|
The following table shows the cable connections for the fourth spine switch
(R4-IB1) when cabling seven full racks together.
Table 110 Leaf Switch Connections for the Fourth Rack in a Seven-Rack System
|
|
|
R4 IB3 within Rack 4
|
R4-IB3-P8A to R4-IB1-P3A
R4-IB3-P8B to R4-IB1-P4A
|
3 meters
|
R4 IB3 to Rack 1
|
R4-IB3-P10B to R1-IB1-P8A
|
10 meters
|
R4 IB3 to Rack 2
|
R4-IB3-P11A to R2-IB1-P9A
|
5 meters
|
R4 IB3 to Rack 3
|
R4-IB3-P11B to R3-IB1-P10A
|
5 meters
|
R4 IB3 to Rack 5
|
R4-IB3-P9A to R5-IB1-P5A
|
5 meters
|
R4 IB3 to Rack 6
|
R4-IB3-P9B to R6-IB1-P6A
|
5 meters
|
R4 IB3 to Rack 7
|
R4-IB3-P10A to R7-IB1-P7A
|
10 meters
|
R4 IB2 within Rack 4
|
R4-IB2-P8A to R4-IB1-P3B
R4-IB2-P8B to R4-IB1-P4B
|
3 meters
|
R4 IB2 to Rack 1
|
R4-IB2-P10B to R1-IB1-P8B
|
10 meters
|
R4 IB2 to Rack 2
|
R4-IB2-P11A to R2-IB1-P9B
|
5 meters
|
R4 IB2 to Rack 3
|
R4-IB2-P11B to R3-IB1-P10B
|
5 meters
|
R4 IB2 to Rack 5
|
R4-IB2-P9A to R5-IB1-P5B
|
5 meters
|
R4 IB2 to Rack 6
|
R4-IB2-P9B to R6-IB1-P6B
|
5 meters
|
R4 IB2 to Rack 7
|
R4-IB2-P10A to R7-IB1-P7B
|
10 meters
|
|
The following table shows the cable connections for the fifth spine switch
(R5-IB1) when cabling seven full racks together.
Table 111 Leaf Switch Connections for the Fifth Rack in a Seven-Rack System
|
|
|
R5 IB3 within Rack 5
|
R5-IB3-P8A to R5-IB1-P3A
R5-IB3-P8B to R5-IB1-P4A
|
3 meters
|
R5 IB3 to Rack 1
|
R5-IB3-P10A to R1-IB1-P7A
|
10 meters
|
R5 IB3 to Rack 2
|
R5-IB3-P10B to R2-IB1-P8A
|
10 meters
|
R5 IB3 to Rack 3
|
R5-IB3-P11A to R3-IB1-P9A
|
5 meters
|
R5 IB3 to Rack 4
|
R5-IB3-P11B to R4-IB1-P10A
|
5 meters
|
R5 IB3 to Rack 6
|
R5-IB3-P9A to R6-IB1-P5A
|
5 meters
|
R5 IB3 to Rack 7
|
R5-IB3-P9B to R7-IB1-P6A
|
5 meters
|
R5 IB2 within Rack 5
|
R5-IB2-P8A to R5-IB1-P3B
R5-IB2-P8B to R5-IB1-P4B
|
3 meters
|
R5 IB2 to Rack 1
|
R5-IB2-P10A to R1-IB1-P7B
|
10 meters
|
R5 IB2 to Rack 2
|
R5-IB2-P10B to R2-IB1-P8B
|
10 meters
|
R5 IB2 to Rack 3
|
R5-IB2-P11A to R3-IB1-P9B
|
5 meters
|
R5 IB2 to Rack 4
|
R5-IB2-P11B to R4-IB1-P10B
|
5 meters
|
R5 IB2 to Rack 6
|
R5-IB2-P9A to R6-IB1-P5B
|
5 meters
|
R5 IB2 to Rack 7
|
R5-IB2-P9B to R7-IB1-P6B
|
5 meters
|
|
The following table shows the cable connections for the sixth spine switch
(R6-IB1) when cabling seven full racks together.
Table 112 Leaf Switch Connections for the Sixth Rack in a Seven-Rack System
|
|
|
R6 IB3 within Rack 6
|
R6-IB3-P8A to R6-IB1-P3A
R6-IB3-P8B to R6-IB1-P4A
|
3 meters
|
R6 IB3 to Rack 1
|
R6-IB3-P9B to R1-IB1-P6A
|
10 meters
|
R6 IB3 to Rack 2
|
R6-IB3-P10A to R2-IB1-P7A
|
10 meters
|
R6 IB3 to Rack 3
|
R6-IB3-P10B to R3-IB1-P8A
|
5 meters
|
R6 IB3 to Rack 4
|
R6-IB3-P11A to R4-IB1-P9A
|
5 meters
|
R6 IB3 to Rack 5
|
R6-IB3-P11B to R5-IB1-P10A
|
5 meters
|
R6 IB3 to Rack 7
|
R6-IB3-P9A to R7-IB1-P5A
|
5 meters
|
R6 IB2 within Rack 6
|
R6-IB2-P8A to R6-IB1-P3B
R6-IB2-P8B to R6-IB1-P4B
|
3 meters
|
R6 IB2 to Rack 1
|
R6-IB2-P9B to R1-IB1-P6B
|
10 meters
|
R6 IB2 to Rack 2
|
R6-IB2-P10A to R2-IB1-P7B
|
10 meters
|
R6 IB2 to Rack 3
|
R6-IB2-P10B to R3-IB1-P8B
|
5 meters
|
R6 IB2 to Rack 4
|
R6-IB2-P11A to R4-IB1-P9B
|
5 meters
|
R6 IB2 to Rack 5
|
R6-IB2-P11B to R5-IB1-P10B
|
5 meters
|
R6 IB2 to Rack 7
|
R6-IB2-P9A to R7-IB1-P5B
|
5 meters
|
|
The following table shows the cable connections for the seventh spine switch
(R7-IB1) when cabling seven full racks together.
Table 113 Leaf Switch Connections for the Seventh Rack in a Seven-Rack System
|
|
|
R7 IB3 within Rack 7
|
R7-IB3-P8A to R7-IB1-P3A
R7-IB3-P8B to R7-IB1-P4A
|
3 meters
|
R7 IB3 to Rack 1
|
R7-IB3-P9A to R1-IB1-P5A
|
10 meters
|
R7 IB3 to Rack 2
|
R7-IB3-P9B to R2-IB1-P6A
|
10 meters
|
R7 IB3 to Rack 3
|
R7-IB3-P10A to R3-IB1-P7A
|
10 meters
|
R7 IB3 to Rack 4
|
R7-IB3-P10B to R4-IB1-P8A
|
10 meters
|
R7 IB3 to Rack 5
|
R7-IB3-P11A to R5-IB1-P9A
|
5 meters
|
R7 IB3 to Rack 6
|
R7-IB3-P11B to R6-IB1-P10A
|
5 meters
|
R7 IB2 within Rack 7
|
R7-IB2-P8A to R7-IB1-P3B
R7-IB2-P8B to R7-IB1-P4B
|
3 meters
|
R7 IB2 to Rack 1
|
R7-IB2-P9A to R1-IB1-P5B
|
10 meters
|
R7 IB2 to Rack 2
|
R7-IB2-P9B to R2-IB1-P6B
|
10 meters
|
R7 IB2 to Rack 3
|
R7-IB2-P10A to R3-IB1-P7B
|
10 meters
|
R7 IB2 to Rack 4
|
R7-IB2-P10B to R4-IB1-P8B
|
10 meters
|
R7 IB2 to Rack 5
|
R7-IB2-P11A to R5-IB1-P9B
|
5 meters
|
R7 IB2 to Rack 6
|
R7-IB2-P11B to R6-IB1-P10B
|
5 meters
|
|
Eight-Rack Cabling
The following table shows the cable connections for the first spine switch
(R1-IB1) when cabling eight full racks together.
Table 114 Leaf Switch Connections for the First Rack in an Eight-Rack System
|
|
|
R1 IB3 within Rack 1
|
R1-IB3-P8A to R1-IB1-P3A
|
3 meters
|
R1 IB3 to Rack 2
|
R1-IB3-P8B to R2-IB1-P4A
|
5 meters
|
R1 IB3 to Rack 3
|
R1-IB3-P9A to R3-IB1-P5A
|
5 meters
|
R1 IB3 to Rack 4
|
R1-IB3-P9B to R4-IB1-P6A
|
10 meters
|
R1 IB3 to Rack 5
|
R1-IB3-P10A to R5-IB1-P7A
|
10 meters
|
R1 IB3 to Rack 6
|
R1-IB3-P10B to R6-IB1-P8A
|
10 meters
|
R1 IB3 to Rack 7
|
R1-IB3-P11A to R7-IB1-P9A
|
10 meters
|
R1 IB3 to Rack 8
|
R1-IB3-P11B to R8-IB1-P10A
|
10 meters
|
R1 IB2 within Rack 1
|
R1-IB2-P8A to R1-IB1-P3B
|
3 meters
|
R1 IB2 to Rack 2
|
R1-IB2-P8B to R2-IB1-P4B
|
5 meters
|
R1 IB2 to Rack 3
|
R1-IB2-P9A to R3-IB1-P5B
|
5 meters
|
R1 IB2 to Rack 4
|
R1-IB2-P9B to R4-IB1-P6B
|
10 meters
|
R1 IB2 to Rack 5
|
R1-IB2-P10A to R5-IB1-P7B
|
10 meters
|
R1 IB2 to Rack 6
|
R1-IB2-P10B to R6-IB1-P8B
|
10 meters
|
R1 IB2 to Rack 7
|
R1-IB2-P11A to R7-IB1-P8B
|
10 meters
|
R1 IB2 to Rack 8
|
R1-IB2-P11B to R8-IB1-P10B
|
10 meters
|
|
The following table shows the cable connections for the second spine switch
(R2-IB1) when cabling eight full racks together.
Table 115 Leaf Switch Connections for the Second Rack in an Eight-Rack System
|
|
|
R2 IB3 within Rack 2
|
R2-IB3-P8A to R2-IB1-P3A
|
3 meters
|
R2 IB3 to Rack 1
|
R2-IB3-P11B to R1-IB1-P10A
|
5 meters
|
R2 IB3 to Rack 3
|
R2-IB3-P8B to R3-IB1-P4A
|
5 meters
|
R2 IB3 to Rack 4
|
R2-IB3-P9A to R4-IB1-P5A
|
5 meters
|
R2 IB3 to Rack 5
|
R2-IB3-P9B to R5-IB1-P6A
|
10 meters
|
R2 IB3 to Rack 6
|
R2-IB3-P10A to R6-IB1-P7A
|
10 meters
|
R2 IB3 to Rack 7
|
R2-IB3-P10B to R7-IB1-P8A
|
10 meters
|
R2 IB3 to Rack 8
|
R2-IB3-P11A to R8-IB1-P9A
|
10 meters
|
R2 IB2 within Rack 2
|
R2-IB2-P8A to R2-IB1-P3B
|
3 meters
|
R2 IB2 to Rack 1
|
R2-IB2-P11B to R1-IB1-P10B
|
5 meters
|
R2 IB2 to Rack 3
|
R2-IB2-P8B to R3-IB1-P4B
|
5 meters
|
R2 IB2 to Rack 4
|
R2-IB2-P9A to R4-IB1-P5B
|
5 meters
|
R2 IB2 to Rack 5
|
R2-IB2-P9B to R5-IB1-P6B
|
10 meters
|
R2 IB2 to Rack 6
|
R2-IB2-P10A to R6-IB1-P7B
|
10 meters
|
R2 IB2 to Rack 7
|
R2-IB2-P10B to R7-IB1-P8B
|
10 meters
|
R2 IB2 to Rack 8
|
R2-IB2-P11A to R8-IB1-P9B
|
10 meters
|
|
The following table shows the cable connections for the third spine switch
(R3-IB1) when cabling eight full racks together.
Table 116 Leaf Switch Connections for the Third Rack in an Eight-Rack System
|
|
|
R3 IB3 within Rack 3
|
R3-IB3-P8A to R3-IB1-P3A
|
3 meters
|
R3 IB3 to Rack 1
|
R3-IB3-P11A to R1-IB1-P9A
|
5 meters
|
R3 IB3 to Rack 2
|
R3-IB3-P11B to R2-IB1-P10A
|
5 meters
|
R3 IB3 to Rack 4
|
R3-IB3-P8B to R4-IB1-P4A
|
5 meters
|
R3 IB3 to Rack 5
|
R3-IB3-P9A to R5-IB1-P5A
|
5 meters
|
R3 IB3 to Rack 6
|
R3-IB3-P9B to R6-IB1-P6A
|
5 meters
|
R3 IB3 to Rack 7
|
R3-IB3-P10A to R7-IB1-P7A
|
10 meters
|
R3 IB3 to Rack 8
|
R3-IB3-P10B to R8-IB1-P8A
|
10 meters
|
R3 IB2 within Rack 3
|
R3-IB2-P8A to R3-IB1-P3B
|
3 meters
|
R3 IB2 to Rack 1
|
R3-IB2-P11A to R1-IB1-P9B
|
5 meters
|
R3 IB2 to Rack 2
|
R3-IB2-P11B to R2-IB1-P10B
|
5 meters
|
R3 IB2 to Rack 4
|
R3-IB2-P8B to R4-IB1-P4B
|
5 meters
|
R3 IB2 to Rack 5
|
R3-IB2-P9A to R5-IB1-P5B
|
5 meters
|
R3 IB2 to Rack 6
|
R3-IB2-P9B to R6-IB1-P6B
|
5 meters
|
R3 IB2 to Rack 7
|
R3-IB2-P10A to R7-IB1-P7B
|
10 meters
|
R3 IB2 to Rack 8
|
R3-IB2-P10B to R8-IB1-P8B
|
10 meters
|
|
The following table shows the cable connections for the fourth spine switch
(R4-IB1) when cabling eight full racks together.
Table 117 Leaf Switch Connections for the Fourth Rack in an Eight-Rack System
|
|
|
R4 IB3 within Rack 4
|
R4-IB3-P8A to R4-IB1-P3A
|
3 meters
|
R4 IB3 to Rack 1
|
R4-IB3-P10B to R1-IB1-P8A
|
10 meters
|
R4 IB3 to Rack 2
|
R4-IB3-P11A to R2-IB1-P9A
|
5 meters
|
R4 IB3 to Rack 3
|
R4-IB3-P11B to R3-IB1-P10A
|
5 meters
|
R4 IB3 to Rack 5
|
R4-IB3-P8B to R5-IB1-P4A
|
5 meters
|
R4 IB3 to Rack 6
|
R4-IB3-P9A to R6-IB1-P5A
|
5 meters
|
R4 IB3 to Rack 7
|
R4-IB3-P9B to R7-IB1-P6A
|
10 meters
|
R4 IB3 to Rack 8
|
R4-IB3-P10A to R8-IB1-P7A
|
10 meters
|
R4 IB2 within Rack 4
|
R4-IB2-P8A to R4-IB1-P3B
|
3 meters
|
R4 IB2 to Rack 1
|
R4-IB2-P10B to R1-IB1-P8B
|
10 meters
|
R4 IB2 to Rack 2
|
R4-IB2-P11A to R2-IB1-P9B
|
5 meters
|
R4 IB2 to Rack 3
|
R4-IB2-P11B to R3-IB1-P10B
|
5 meters
|
R4 IB2 to Rack 5
|
R4-IB2-P8B to R5-IB1-P4B
|
5 meters
|
R4 IB2 to Rack 6
|
R4-IB2-P9A to R6-IB1-P5B
|
5 meters
|
R4 IB2 to Rack 7
|
R4-IB2-P9B to R7-IB1-P6B
|
10 meters
|
R4 IB2 to Rack 8
|
R4-IB2-P10A to R8-IB1-P7B
|
10 meters
|
|
The following table shows the cable connections for the fifth spine switch
(R5-IB1) when cabling eight full racks together.
Table 118 Leaf Switch Connections for the Fifth Rack in an Eight-Rack System
|
|
|
R5 IB3 within Rack 5
|
R5-IB3-P8A to R5-IB1-P3A
|
3 meters
|
R5 IB3 to Rack 1
|
R5-IB3-P10A to R1-IB1-P7A
|
10 meters
|
R5 IB3 to Rack 2
|
R5-IB3-P10B to R2-IB1-P8A
|
10 meters
|
R5 IB3 to Rack 3
|
R5-IB3-P11A to R3-IB1-P9A
|
5 meters
|
R5 IB3 to Rack 4
|
R5-IB3-P11B to R4-IB1-P10A
|
5 meters
|
R5 IB3 to Rack 6
|
R5-IB3-P8B to R6-IB1-P4A
|
5 meters
|
R5 IB3 to Rack 7
|
R5-IB3-P9A to R7-IB1-P5A
|
5 meters
|
R5 IB3 to Rack 8
|
R5-IB3-P9B to R8-IB1-P6A
|
10 meters
|
R5 IB2 within Rack 5
|
R5-IB2-P8A to R5-IB1-P3B
|
3 meters
|
R5 IB2 to Rack 1
|
R5-IB2-P10A to R1-IB1-P7B
|
10 meters
|
R5 IB2 to Rack 2
|
R5-IB2-P10B to R2-IB1-P8B
|
10 meters
|
R5 IB2 to Rack 3
|
R5-IB2-P11A to R3-IB1-P9B
|
5 meters
|
R5 IB2 to Rack 4
|
R5-IB2-P11B to R4-IB1-P10B
|
5 meters
|
R5 IB2 to Rack 6
|
R5-IB2-P8B to R6-IB1-P4B
|
5 meters
|
R5 IB2 to Rack 7
|
R5-IB2-P9A to R7-IB1-P5B
|
5 meters
|
R5 IB2 to Rack 8
|
R5-IB2-P9B to R8-IB1-P6B
|
10 meters
|
|
The following table shows the cable connections for the sixth spine switch
(R6-IB1) when cabling eight full racks together.
Table 119 Leaf Switch Connections for the Sixth Rack in an Eight-Rack System
|
|
|
R6 IB3 within Rack 6
|
R6-IB3-P8A to R6-IB1-P3A
|
3 meters
|
R6 IB3 to Rack 1
|
R6-IB3-P9B to R1-IB1-P6A
|
10 meters
|
R6 IB3 to Rack 2
|
R6-IB3-P10A to R2-IB1-P7A
|
10 meters
|
R6 IB3 to Rack 3
|
R6-IB3-P10B to R3-IB1-P8A
|
5 meters
|
R6 IB3 to Rack 4
|
R6-IB3-P11A to R4-IB1-P9A
|
5 meters
|
R6 IB3 to Rack 5
|
R6-IB3-P11B to R5-IB1-P10A
|
5 meters
|
R6 IB3 to Rack 7
|
R6-IB3-P8B to R7-IB1-P4A
|
5 meters
|
R6 IB3 to Rack 8
|
R6-IB3-P9A to R8-IB1-P5A
|
5 meters
|
R6 IB2 within Rack 6
|
R6-IB2-P8A to R6-IB1-P3B
|
3 meters
|
R6 IB2 to Rack 1
|
R6-IB2-P9B to R1-IB1-P6B
|
10 meters
|
R6 IB2 to Rack 2
|
R6-IB2-P10A to R2-IB1-P7B
|
10 meters
|
R6 IB2 to Rack 3
|
R6-IB2-P10B to R3-IB1-P8B
|
5 meters
|
R6 IB2 to Rack 4
|
R6-IB2-P11A to R4-IB1-P9B
|
5 meters
|
R6 IB2 to Rack 5
|
R6-IB2-P11B to R5-IB1-P10B
|
5 meters
|
R6 IB2 to Rack 7
|
R6-IB2-P8B to R7-IB1-P4B
|
5 meters
|
R6 IB2 to Rack 8
|
R6-IB2-P9A to R8-IB1-P5B
|
5 meters
|
|
The following table shows the cable connections for the seventh spine switch
(R7-IB1) when cabling eight full racks together.
Table 120 Leaf Switch Connections for the Seventh Rack in an Eight-Rack System
|
|
|
R7 IB3 within Rack 7
|
R7-IB3-P8A to R7-IB1-P3A
|
3 meters
|
R7 IB3 to Rack 1
|
R7-IB3-P9A to R1-IB1-P5A
|
10 meters
|
R7 IB3 to Rack 2
|
R7-IB3-P9B to R2-IB1-P6A
|
10 meters
|
R7 IB3 to Rack 3
|
R7-IB3-P10A to R3-IB1-P7A
|
10 meters
|
R7 IB3 to Rack 4
|
R7-IB3-P10B to R4-IB1-P8A
|
10 meters
|
R7 IB3 to Rack 5
|
R7-IB3-P11A to R5-IB1-P9A
|
5 meters
|
R7 IB3 to Rack 6
|
R7-IB3-P11B to R6-IB1-P10A
|
5 meters
|
R7 IB3 to Rack 8
|
R7-IB3-P8B to R8-IB1-P4A
|
5 meters
|
R7 IB2 within Rack 7
|
R7-IB2-P8A to R7-IB1-P3B
|
3 meters
|
R7 IB2 to Rack 1
|
R7-IB2-P9A to R1-IB1-P5B
|
10 meters
|
R7 IB2 to Rack 2
|
R7-IB2-P9B to R2-IB1-P6B
|
10 meters
|
R7 IB2 to Rack 3
|
R7-IB2-P10A to R3-IB1-P7B
|
10 meters
|
R7 IB2 to Rack 4
|
R7-IB2-P10B to R4-IB1-P8B
|
10 meters
|
R7 IB2 to Rack 5
|
R7-IB2-P11A to R5-IB1-P9B
|
5 meters
|
R7 IB2 to Rack 6
|
R7-IB2-P11B to R6-IB1-P10B
|
5 meters
|
R7 IB2 to Rack 8
|
R7-IB2-P8B to R8-IB1-P4B
|
5 meters
|
|
The following table shows the cable connections for the eighth spine switch
(R8-IB1) when cabling eight full racks together.
Table 121 Leaf Switch Connections for the Eighth Rack in an Eight-Rack System
|
|
|
R8 IB3 within Rack 8
|
R8-IB3-P8A to R8-IB1-P3A
|
3 meters
|
R8 IB3 to Rack 1
|
R8-IB3-P8B to R1-IB1-P4A
|
10 meters
|
R8 IB3 to Rack 2
|
R8-IB3-P9A to R2-IB1-P5A
|
10 meters
|
R8 IB3 to Rack 3
|
R8-IB3-P9B to R3-IB1-P6A
|
10 meters
|
R8 IB3 to Rack 4
|
R8-IB3-P10A to R4-IB1-P7A
|
10 meters
|
R8 IB3 to Rack 5
|
R8-IB3-P10B to R5-IB1-P8A
|
5 meters
|
R8 IB3 to Rack 6
|
R8-IB3-P11A to R6-IB1-P9A
|
5 meters
|
R8 IB3 to Rack 7
|
R8-IB3-P11B to R7-IB1-P10A
|
5 meters
|
R8 IB2 within Rack 8
|
R8-IB2-P8A to R8-IB1-P3B
|
3 meters
|
R8 IB2 to Rack 1
|
R8-IB2-P8B to R1-IB1-P4B
|
10 meters
|
R8 IB2 to Rack 2
|
R8-IB2-P9A to R2-IB1-P5B
|
10 meters
|
R8 IB2 to Rack 3
|
R8-IB2-P9B to R3-IB1-P6B
|
10 meters
|
R8 IB2 to Rack 4
|
R8-IB2-P10A to R4-IB1-P7B
|
10 meters
|
R8 IB2 to Rack 5
|
R8-IB2-P10B to R5-IB1-P8B
|
5 meters
|
R8 IB2 to Rack 6
|
R8-IB2-P11A to R6-IB1-P9B
|
5 meters
|
R8 IB2 to Rack 7
|
R8-IB2-P1B to R7-IB1-P10B
|
5 meters
|
|
Nine-Rack Cabling
The following table shows the cable connections for the switches when cabling nine
racks together.
Note -
Cable lengths for racks 9 through 18 vary depending on the layout of the
racks. Up to 100 meters is supported.
Table 122 Leaf Switch Connection for the Ninth Rack in the System
|
|
R9 IB3 to Rack 1
|
R9-IB3-P8B to R1-IB1-P11A
|
R9 IB3 to Rack 2
|
R9-IB3-P9A to R2-IB1-P11A
|
R9 IB3 to Rack 3
|
R9-IB3-P9B to R3-IB1-P11A
|
R9 IB3 to Rack 4
|
R9-IB3-P10A to R4-IB1-P11A
|
R9 IB3 to Rack 5
|
R9-IB3-P10B to R5-IB1-P11A
|
R9 IB3 to Rack 6
|
R9-IB3-P11A to R6-IB1-P11A
|
R9 IB3 to Rack 7
|
R9-IB3-P11B to R7-IB1-P11A
|
R9 IB3 to Rack 8
|
R9-IB3-P9A to R8-IB1-P11A
|
R9 IB2 to Rack 1
|
R9-IB2-P8B to R1-IB1-P11B
|
R9 IB2 to Rack 2
|
R9-IB2-P9A to R2-IB1-P11B
|
R9 IB2 to Rack 3
|
R9-IB2-P9B to R3-IB1-P11B
|
R9 IB2 to Rack 4
|
R9-IB2-P10A to R4-IB1-P11B
|
R9 IB2 to Rack 5
|
R9-IB2-P10B to R5-IB1-P11B
|
R9 IB2 to Rack 6
|
R9-IB2-P11A to R6-IB1-P11B
|
R9 IB2 to Rack 7
|
R9-IB2-P11B to R7-IB1-P11B
|
R9 IB2 to Rack 8
|
R9-IB2-P8A to R8-IB1-P11B
|
|
Ten-Rack Cabling
The following table shows the cable connections for the switches when cabling ten
racks together.
Note -
Cable lengths for racks 9 through 18 vary depending on the layout of the
racks. Up to 100 meters is supported.
Table 123 Leaf Switch Connections for the Tenth Rack in the System
|
|
R10 IB3 to Rack 1
|
R10-IB3-P8B to R1-IB1-P12A
|
R10 IB3 to Rack 2
|
R10-IB3-P9A to R2-IB1-P12A
|
R10 IB3 to Rack 3
|
R10-IB3-P9B to R3-IB1-P12A
|
R10 IB3 to Rack 4
|
R10-IB3-P10A to R4-IB1-P12A
|
R10 IB3 to Rack 5
|
R10-IB3-P10B to R5-IB1-P12A
|
R10 IB3 to Rack 6
|
R10-IB3-P12A to R6-IB1-P12A
|
R10 IB3 to Rack 7
|
R10-IB3-P12B to R7-IB1-P12A
|
R10 IB3 to Rack 8
|
R10-IB3-P8A to R8-IB1-P12A
|
R10 IB2 to Rack 1
|
R10-IB2-P8B to R1-IB1-P12B
|
R10 IB2 to Rack 2
|
R10-IB2-P9A to R2-IB1-P12B
|
R10 IB2 to Rack 3
|
R10-IB2-P9B to R3-IB1-P12B
|
R10 IB2 to Rack 4
|
R10-IB2-P10A to R4-IB1-P12B
|
R10 IB2 to Rack 5
|
R10-IB2-P10B to R5-IB1-P12B
|
R10 IB2 to Rack 6
|
R10-IB2-P12A to R6-IB1-P12B
|
R10 IB2 to Rack 7
|
R10-IB2-P12B to R7-IB1-P12B
|
R10 IB2 to Rack 8
|
R10-IB2-P8A to R8-IB1-P12B
|
|
Eleven-Rack Cabling
The following table shows the cable connections for the switches when cabling
eleven racks together.
Note -
Cable lengths for racks 9 through 18 vary depending on the layout of the
racks. Up to 100 meters is supported.
Table 124 Leaf Switch Connections for the Eleventh Rack in the System
|
|
R11 IB3 to Rack 1
|
R11-IB3-P8B to R1-IB1-P13A
|
R11 IB3 to Rack 2
|
R11-IB3-P9A to R2-IB1-P13A
|
R11 IB3 to Rack 3
|
R11-IB3-P9B to R3-IB1-P13A
|
R11 IB3 to Rack 4
|
R11-IB3-P10A to R4-IB1-P13A
|
R11 IB3 to Rack 5
|
R11-IB3-P10B to R5-IB1-P13A
|
R11 IB3 to Rack 6
|
R11-IB3-P13A to R6-IB1-P13A
|
R11 IB3 to Rack 7
|
R11-IB3-P13B to R7-IB1-P13A
|
R11 IB3 to Rack 8
|
R11-IB3-P8A to R8-IB1-P13A
|
R11 IB2 to Rack 1
|
R11-IB2-P8B to R1-IB1-P13B
|
R11 IB2 to Rack 2
|
R11-IB2-P9A to R2-IB1-P13B
|
R11 IB2 to Rack 3
|
R11-IB2-P9B to R3-IB1-P13B
|
R11 IB2 to Rack 4
|
R11-IB2-P10A to R4-IB1-P13B
|
R11 IB2 to Rack 5
|
R11-IB2-P10B to R5-IB1-P13B
|
R11 IB2 to Rack 6
|
R11-IB2-P13A to R6-IB1-P13B
|
R11 IB2 to Rack 7
|
R11-IB2-P13B to R7-IB1-P13B
|
R11 IB2 to Rack 8
|
R11-IB2-P8A to R8-IB1-P13B
|
|
Twelve-Rack Cabling
The following table shows the cable connections for the switches when cabling
twelve racks together.
Note -
Cable lengths for racks 9 through 18 vary depending on the layout of the
racks. Up to 100 meters is supported.
Table 125 Leaf Switch Connections for the Twelfth Rack in the System
|
|
R12 IB3 to Rack 1
|
R12-IB3-P8B to R1-IB1-P14A
|
R12 IB3 to Rack 2
|
R12-IB3-P9A to R2-IB1-P14A
|
R12 IB3 to Rack 3
|
R12-IB3-P9B to R3-IB1-P14A
|
R12 IB3 to Rack 4
|
R12-IB3-P10A to R4-IB1-P14A
|
R12 IB3 to Rack 5
|
R12-IB3-P10B to R5-IB1-P14A
|
R12 IB3 to Rack 6
|
R12-IB3-P14A to R6-IB1-P14A
|
R12 IB3 to Rack 7
|
R12-IB3-P14B to R7-IB1-P14A
|
R12 IB3 to Rack 8
|
R12-IB3-P8A to R8-IB1-P14A
|
R12 IB2 to Rack 1
|
R12-IB2-P8B to R1-IB1-P14B
|
R12 IB2 to Rack 2
|
R12-IB2-P9A to R2-IB1-P14B
|
R12 IB2 to Rack 3
|
R12-IB2-P9B to R3-IB1-P14B
|
R12 IB2 to Rack 4
|
R12-IB2-P10A to R4-IB1-P14B
|
R12 IB2 to Rack 5
|
R12-IB2-P10B to R5-IB1-P14B
|
R12 IB2 to Rack 6
|
R12-IB2-P14A to R6-IB1-P14B
|
R12 IB2 to Rack 7
|
R12-IB2-P14B to R7-IB1-P14B
|
R12 IB2 to Rack 8
|
R12-IB2-P8A to R8-IB1-P14B
|
|
Thirteen-Rack Cabling
The following table shows the cable connections for the switches when cabling
thirteen racks together.
Note -
Cable lengths for racks 9 through 18 vary depending on the layout of the
racks. Up to 100 meters is supported.
Table 126 Leaf Switch Connections for the Thirteenth Rack in the System
|
|
R13 IB3 to Rack 1
|
R13-IB3-P8B to R1-IB1-P15A
|
R13 IB3 to Rack 2
|
R13-IB3-P9A to R2-IB1-P15A
|
R13 IB3 to Rack 3
|
R13-IB3-P9B to R3-IB1-P15A
|
R13 IB3 to Rack 4
|
R13-IB3-P10A to R4-IB1-P15A
|
R13 IB3 to Rack 5
|
R13-IB3-P10B to R5-IB1-P15A
|
R13 IB3 to Rack 6
|
R13-IB3-P15A to R6-IB1-P15A
|
R13 IB3 to Rack 7
|
R13-IB3-P15B to R7-IB1-P15A
|
R13 IB3 to Rack 8
|
R13-IB3-P8A to R8-IB1-P15A
|
R13 IB2 to Rack 1
|
R13-IB2-P8B to R1-IB1-P15B
|
R13 IB2 to Rack 2
|
R13-IB2-P9A to R2-IB1-P15B
|
R13 IB2 to Rack 3
|
R13-IB2-P9B to R3-IB1-P15B
|
R13 IB2 to Rack 4
|
R13-IB2-P10A to R4-IB1-P15B
|
R13 IB2 to Rack 5
|
R13-IB2-P10B to R5-IB1-P15B
|
R13 IB2 to Rack 6
|
R13-IB2-P15A to R6-IB1-P15B
|
R13 IB2 to Rack 7
|
R13-IB2-P15B to R7-IB1-P15B
|
R13 IB2 to Rack 8
|
R13-IB2-P8A to R8-IB1-P15B
|
|
Fourteen-Rack Cabling
The following table shows the cable connections for the switches when cabling
fourteen racks together.
Note -
Cable lengths for racks 9 through 18 vary depending on the layout of the
racks. Up to 100 meters is supported.
Table 127 Leaf Switch Connections for the Fourteenth Rack in the System
|
|
R14 IB3 to Rack 1
|
R14-IB3-P8B to R1-IB1-P16A
|
R14 IB3 to Rack 2
|
R14-IB3-P9A to R2-IB1-P16A
|
R14 IB3 to Rack 3
|
R14-IB3-P9B to R3-IB1-P16A
|
R14 IB3 to Rack 4
|
R14-IB3-P10A to R4-IB1-P16A
|
R14 IB3 to Rack 5
|
R14-IB3-P10B to R5-IB1-P16A
|
R14 IB3 to Rack 6
|
R14-IB3-P16A to R6-IB1-P16A
|
R14 IB3 to Rack 7
|
R14-IB3-P16B to R7-IB1-P16A
|
R14 IB3 to Rack 8
|
R14-IB3-P8A to R8-IB1-P16A
|
R14 IB2 to Rack 1
|
R14-IB2-P8B to R1-IB1-P16B
|
R14 IB2 to Rack 2
|
R14-IB2-P9A to R2-IB1-P16B
|
R14 IB2 to Rack 3
|
R14-IB2-P9B to R3-IB1-P16B
|
R14 IB2 to Rack 4
|
R14-IB2-P10A to R4-IB1-P16B
|
R14 IB2 to Rack 5
|
R14-IB2-P10B to R5-IB1-P16B
|
R14 IB2 to Rack 6
|
R14-IB2-P16A to R6-IB1-P16B
|
R14 IB2 to Rack 7
|
R14-IB2-P16B to R7-IB1-P16B
|
R14 IB2 to Rack 8
|
R14-IB2-P8A to R8-IB1-P16B
|
|
Fifteen-Rack Cabling
The following table shows the cable connections for the switches when cabling
fifteen racks together.
Note -
Cable lengths for racks 9 through 18 vary depending on the layout of the
racks. Up to 100 meters is supported.
Table 128 Leaf Switch Connections for the Fifteenth Rack in the System
|
|
R15 IB3 to Rack 1
|
R15-IB3-P8B to R1-IB1-P17A
|
R15 IB3 to Rack 2
|
R15-IB3-P9A to R2-IB1-P17A
|
R15 IB3 to Rack 3
|
R15-IB3-P9B to R3-IB1-P17A
|
R15 IB3 to Rack 4
|
R15-IB3-P10A to R4-IB1-P17A
|
R15 IB3 to Rack 5
|
R15-IB3-P10B to R5-IB1-P17A
|
R15 IB3 to Rack 6
|
R15-IB3-P17A to R6-IB1-P17A
|
R15 IB3 to Rack 7
|
R15-IB3-P17B to R7-IB1-P17A
|
R15 IB3 to Rack 8
|
R15-IB3-P8A to R8-IB1-P17A
|
R15 IB2 to Rack 1
|
R15-IB2-P8B to R1-IB1-P17B
|
R15 IB2 to Rack 2
|
R15-IB2-P9A to R2-IB1-P17B
|
R15 IB2 to Rack 3
|
R15-IB2-P9B to R3-IB1-P17B
|
R15 IB2 to Rack 4
|
R15-IB2-P10A to R4-IB1-P17B
|
R15 IB2 to Rack 5
|
R15-IB2-P10B to R5-IB1-P17B
|
R15 IB2 to Rack 6
|
R15-IB2-P17A to R6-IB1-P17B
|
R15 IB2 to Rack 7
|
R15-IB2-P17B to R7-IB1-P17B
|
R15 IB2 to Rack 8
|
R15-IB2-P8A to R8-IB1-P17B
|
|
Sixteen-Rack Cabling
The following table shows the cable connections for the switches when cabling
sixteen racks together.
Note -
Cable lengths for racks 9 through 18 vary depending on the layout of the
racks. Up to 100 meters is supported.
Table 129 Leaf Switch Connections for the Sixteenth Rack in the System
|
|
R16 IB3 to Rack 1
|
R16-IB3-P8B to R1-IB1-P0A
|
R16 IB3 to Rack 2
|
R16-IB3-P9A to R2-IB1-P0A
|
R16 IB3 to Rack 3
|
R16-IB3-P9B to R3-IB1-P0A
|
R16 IB3 to Rack 4
|
R16-IB3-P10A to R4-IB1-P0A
|
R16 IB3 to Rack 5
|
R16-IB3-P10B to R5-IB1-P0A
|
R16 IB3 to Rack 6
|
R16-IB3-P0A to R6-IB1-P0A
|
R16 IB3 to Rack 7
|
R16-IB3-P0B to R7-IB1-P0A
|
R16 IB3 to Rack 8
|
R16-IB3-P8A to R8-IB1-P0A
|
R16 IB2 to Rack 1
|
R16-IB2-P8B to R1-IB1-P0B
|
R16 IB2 to Rack 2
|
R16-IB2-P9A to R2-IB1-P0B
|
R16 IB2 to Rack 3
|
R16-IB2-P9B to R3-IB1-P0B
|
R16 IB2 to Rack 4
|
R16-IB2-P10A to R4-IB1-P0B
|
R16 IB2 to Rack 5
|
R16-IB2-P10B to R5-IB1-P0B
|
R16 IB2 to Rack 6
|
R16-IB2-P0A to R6-IB1-P0B
|
R16 IB2 to Rack 7
|
R16-IB2-P0B to R7-IB1-P0B
|
R16 IB2 to Rack 8
|
R16-IB2-P8A to R8-IB1-P0B
|
|
Seventeen-Rack Cabling
The following table shows the cable connections for the switches when cabling
seventeen racks together.
Note -
Cable lengths for racks 9 through 18 vary depending on the layout of the
racks. Up to 100 meters is supported.
Table 130 Leaf Switch Connections for the Seventeenth Rack in the System
|
|
R17 IB3 to Rack 1
|
R17-IB3-P8B to R1-IB1-P1A
|
R17 IB3 to Rack 2
|
R17-IB3-P9A to R2-IB1-P1A
|
R17 IB3 to Rack 3
|
R17-IB3-P9B to R3-IB1-P1A
|
R17 IB3 to Rack 4
|
R17-IB3-P10A to R4-IB1-P1A
|
R17 IB3 to Rack 5
|
R17-IB3-P10B to R5-IB1-P1A
|
R17 IB3 to Rack 6
|
R17-IB3-P1A to R6-IB1-P1A
|
R17 IB3 to Rack 7
|
R17-IB3-P1B to R7-IB1-P1A
|
R17 IB3 to Rack 8
|
R17-IB3-P8A to R8-IB1-P1A
|
R17 IB2 to Rack 1
|
R17-IB2-P8B to R1-IB1-P1B
|
R17 IB2 to Rack 2
|
R17-IB2-P9A to R2-IB1-P1B
|
R17 IB2 to Rack 3
|
R17-IB2-P9B to R3-IB1-P1B
|
R17 IB2 to Rack 4
|
R17-IB2-P10A to R4-IB1-P1B
|
R17 IB2 to Rack 5
|
R17-IB2-P10B to R5-IB1-P1B
|
R17 IB2 to Rack 6
|
R17-IB2-P1A to R6-IB1-P1B
|
R17 IB2 to Rack 7
|
R17-IB2-P1B to R7-IB1-P1B
|
R17 IB2 to Rack 8
|
R17-IB2-P8A to R8-IB1-P1B
|
|
Eighteen-Rack Cabling
The following table shows the cable connections for the switches when cabling
eighteen racks together.
Note -
Cable lengths for racks 9 through 18 vary depending on the layout of the
racks. Up to 100 meters is supported.
Table 131 Leaf Switch Connections for the Eighteenth Rack in the System
|
|
R18 IB3 to Rack 1
|
R18-IB3-P8B to R1-IB1-P2A
|
R18 IB3 to Rack 2
|
R18-IB3-P9A to R2-IB1-P2A
|
R18 IB3 to Rack 3
|
R18-IB3-P9B to R3-IB1-P2A
|
R18 IB3 to Rack 4
|
R18-IB3-P10A to R4-IB1-P2A
|
R18 IB3 to Rack 5
|
R18-IB3-P10B to R5-IB1-P2A
|
R18 IB3 to Rack 6
|
R18-IB3-P2A to R6-IB1-P2A
|
R18 IB3 to Rack 7
|
R18-IB3-P2B to R7-IB1-P2A
|
R18 IB3 to Rack 8
|
R18-IB3-P8A to R8-IB1-P2A
|
R18 IB2 to Rack 1
|
R18-IB2-P8B to R1-IB1-P2B
|
R18 IB2 to Rack 2
|
R18-IB2-P9A to R2-IB1-P2B
|
R18 IB2 to Rack 3
|
R18-IB2-P9B to R3-IB1-P2B
|
R18 IB2 to Rack 4
|
R18-IB2-P10A to R4-IB1-P2B
|
R18 IB2 to Rack 5
|
R18-IB2-P10B to R5-IB1-P2B
|
R18 IB2 to Rack 6
|
R18-IB2-P2A to R6-IB1-P2B
|
R18 IB2 to Rack 7
|
R18-IB2-P2B to R7-IB1-P2B
|
R18 IB2 to Rack 8
|
R18-IB2-P8A to R8-IB1-P2B
|
|