Power Consumption

These tables describe power consumption of SuperCluster T5-8 and expansion racks.

These are measured values and not the rated power for the rack. For rated power specifications, see PDU Power Requirements.

Table 4  SuperCluster T5-8
Condition
Full Rack
Half Rack
Maximum
Typical
15.97 kVA
15.17 kW
13.31 kVA
12.64 kW
9.09 kVA
8.6 kW
7.5 kVA
7.13 kW
Table 5  Exadata X5-2 Expansion Rack
Product
Condition
kW
kVA
Extreme Flash quarter rack
Maximum
Typical
3.6
2.5
3.7
2.6
High capacity quarter rack
Maximum
Typical
3.4
2.4
3.4
2.4
Individual Extreme Flash storage server
Maximum
Typical
.6
.4
.6
.4
Individual High capacity storage server
Maximum
Typical
.5
.4
.5
.4