Oracle® SuperCluster T5-8 Owner's Guide

Exit Print View

Updated: May 2016
 
 

Two-Rack Cabling

The following table shows the cable connections for the first spine switch (R1-U1) when cabling two full racks together.

Table 22  Leaf Switch Connections for the First Rack in a Two-Rack System
Leaf Switch
Connection
Cable Length
R1-U32 within Rack 1
R1-U32-P8A to R1-U1-P3A
R1-U32-P8B to R1-U1-P4A
R1-U32-P9A to R1-U1-P5A
R1-U32-P9B to R1-U1-P6A
5 meters
R1-U32 to Rack 2
R1-U32-P10A to R2-U1-P7A
R1-U32-P10B to R2-U1-P8A
R1-U32-P11A to R2-U1-P9A
R1-U32-P11B to R2-U1-P10A
5 meters
R1-U26 within Rack 1
R1-U26-P8A to R1-U1-P3B
R1-U26-P8B to R1-U1-P4B
R1-U26-P9A to R1-U1-P5B
R1-U26-P9B to R1-U1-P6B
5 meters
R1-U26 to Rack 2
R1-U26-P10A to R2-U1-P7B
R1-U26-P10B to R2-U1-P8B
R1-U26-P11A to R2-U1-P9B
R1-U26-P11B to R2-U1-P10B
5 meters

The following table shows the cable connections for the second spine switch (R2-U1) when cabling two full racks together.

Table 23  Leaf Switch Connections for the Second Rack in a Two-Rack System
Leaf Switch
Connection
Cable Length
R2-U32 within Rack 2
R2-U32-P8A to R2-U1-P3A
R2-U32-P8B to R2-U1-P4A
R2-U32-P9A to R2-U1-P5A
R2-U32-P9B to R2-U1-P6A
5 meters
R2-U32 to Rack 1
R2-U32-P10A to R1-U1-P7A
R2-U32-P10B to R1-U1-P8A
R2-U32-P11A to R1-U1-P9A
R2-U32-P11B to R1-U1-P10A
5 meters
R2-U26 within Rack 2
R2-U26-P8A to R2-U1-P3B
R2-U26-P8B to R2-U1-P4B
R2-U26-P9A to R2-U1-P5B
R2-U26-P9B to R2-U1-P6B
5 meters
R2-U26 to Rack 1
R2-U26-P10A to R1-U1-P7B
R2-U26-P10B to R1-U1-P8B
R2-U26-P11A to R1-U1-P9B
R2-U26-P11B to R1-U1-P10B
5 meters