Expansion Rack PDU Power Specifications

Use one of these tables to identify the PDU power specifications for your type of expansion rack.

Table 14  Low-Voltage, Single-Phase PDUs
Specification
Requirement for Each PDU
Voltage
200 to 240 VAC
Frequency
50/60 Hz
Current
24A maximum per input
Power rating (11 or fewer storage servers)
15 kVA
Output current
72A (3 inputs x 24A)
Outlets
42 x C13, 6 x C19
Outlet groups
6
Group protection (UL489 2-pole circuit breaker)
20A
Datacenter receptacle
NEMA L6-30R
Table 15  Low-Voltage, Three-Phase PDUs
Specification
Requirement for Each PDU
Voltage
200 to 220 VAC
Frequency
50/60 Hz
Current
40A maximum per phase
Power rating
15 kVA
Output current
69.3A (3 x 23.1A)
Outlets
42 x C13, 6 x C19
Outlet groups
6
Group protection (UL489 2-pole circuit breaker)
20A
Datacenter receptacle
IEC 60309 60A 4-pin 250 VAC three-phase IP67
Table 16  High-Voltage, Single-Phase PDUs
Specification
Requirement for Each PDU
Voltage
220 to 240 VAC
Frequency
50/60 Hz
Current
32A maximum per input
Power rating
22 kVA
Output current
96A (3 x 32A)
Outlets
42 x C13, 6 x C19
Outlet groups
6
Group protection (UL489 1-pole circuit breaker)
20A
Datacenter receptacle
IEC 60309 32A with 3-pin 250 VAC IP44
Table 17  High-Voltage, Three-Phase PDUs
Specification
Requirement for Each PDU
Voltage
220/380 to 240/415 VAC 3 ph
Frequency
50/60 Hz
Current
25A maximum per input
Power rating
15 kVA
Output current
62.7A (3 x 20.9A)
Outlets
42 x C13, 6 x C19
Outlet groups
6
Group protection (UL489 1-pole circuit breaker)
20A
Datacenter receptacle
IEC 60309 32A with 5-pin 230/400V, three-phase IP44