Power Consumption
These tables describe power consumption of SuperCluster M8, SuperCluster M7 and
expansion racks.
These are measured values and not the rated power for the rack. For rated power
specifications, see SuperCluster M8 and SuperCluster M7 PDU Power Specifications and Expansion Rack PDU Power Specifications.
Table 7 SuperCluster M8
|
|
|
|
Single compute server with 3 storage servers
|
Maximum
Typical
|
12,523
9,969
|
13,182
10,494
|
Single compute server with 11 storage servers
|
Maximum
Typical
|
17,153
13,542
|
18,056
14,255
|
Dual compute servers with 6 storage servers
|
Maximum
Typical
|
22,693
17,828
|
23,887
18,767
|
|
Table 8 SuperCluster M7
|
|
|
|
Single compute server with 3 storage servers
|
Maximum
Typical
|
12,088
8,419
|
12,724
8,862
|
Single compute server with 11 storage servers
|
Maximum
Typical
|
15,888
12,874
|
16,724
13,552
|
Dual compute servers with 3 storage servers
|
Maximum
Typical
|
20,258
17,174
|
21,324
18,078
|
Dual compute servers with 6 storage servers
|
Maximum
Typical
|
21,683
18,126
|
22,824
19,080
|
|
Table 9 Expansion Rack
|
|
|
|
EF quarter rack
|
Maximum
Typical
|
3.6
2.5
|
3.7
2.6
|
HC quarter rack
|
Maximum
Typical
|
3.4
2.4
|
3.4
2.4
|
Individual EF storage server
|
Maximum
Typical
|
.6
.4
|
.6
.4
|
Individual HC storage server
|
Maximum
Typical
|
.5
.4
|
.5
.4
|
|