Go to main content

Oracle® SuperCluster M8 and SuperCluster M7 Installation Guide

Exit Print View

Updated: January 2019
 
 

Heat Dissipation Specifications

Table 24  SuperCluster M8 Rack Specifications
Configuration
BTU/Hour
Kj/Hour
Single compute server with 3 storage servers
Maximum
44,978
47,407
Typical
35,807
37,740
Single compute server with 11 storage servers
Maximum
61,609
64,936
Typical
48,639
51,265
Dual compute server with 6 storage servers
Maximum
81,505
85,906
Typical
64,034
67,492
Table 25  SuperCluster M7 Rack Specifications
Configuration
BTU/Hour
Kj/Hour
Single compute server with 3 storage servers
Maximum
43,416
45,780
Typical
30,238
31,871
Single compute server with 11 storage servers
Maximum
57,064
60,145
Typical
46,241
48,738
Dual compute server with 3 storage servers
Maximum
72,760
76,689
Typical
61,684
65,015
Dual compute server with 6 storage servers
Maximum
77,878
82,083
Typical
65,103
68,618
Table 26  Expansion Rack Specifications 
Configuration
BTU/Hour
Kj/Hour
EF quarter rack
Maximum
12,362
13,042
Typical
8,654
9,129
HC quarter rack
Maximum
11,516
12,149
Typical
8,061
8,505
Individual EF storage server
Maximum
2,037
2,149
Typical
1,426
1,504
Individual HC storage server
Maximum
1,825
1,926
Typical
1,278
1,348

Related Information