PDU Thresholds (Dual-Server Model With 6 Storage Servers)

Table 22  22 kVA Single-Phase PDUs
Low Voltage
Low Voltage
High Voltage
High Voltage
PDU A
PDU B
Warning (Amps)
Alarm (Amps)
Warning (Amps)
Alarm (Amps)
M1-3
M1-1
28
36
26
32
M1-2
M1-2
27
35
25
32
M1-1
M1-3
29
36
26
32
Table 23  24 kVA 3-Phase PDUs
Low Voltage
Low Voltage
High Voltage
High Voltage
PDU A
PDU B
Warning (Amps)
Alarm (Amps)
Warning (Amps)
Alarm (Amps)
M2-3
M1-3
25
31
13
17
M2-2
M1-2
25
32
13
17
M2-1
M1-1
25
32
14
18
M1-3
M2-3
24
31
13
16
M1-2
M2-2
24
30
13
17
M1-1
M2-1
23
30
12
16