SuperCluster M8 and SuperCluster M7 PDU Power Specifications
When ordering SuperCluster M8 or SuperCluster M7, you must provide two
specifications for the racks:
Use one of these tables to identify the PDU power specifications for your type of
rack.
Table 10 Low-Voltage, Single-Phase PDUs
|
|
Voltage
|
200 to 240 VAC
|
Frequency
|
50/60 Hz
|
Current
|
35.4A max. per input
|
Power rating
|
22 kVA
|
Output current
|
120A (6 x 20A)
|
Outlets
|
42 x C13, 6 x C19
|
Outlet groups
|
6
|
Group protection (UL489 2-pole circuit breaker)
|
20A
|
Datacenter receptacle
|
Hubbell CS8264C
|
Number of inputs
|
3 x 50A 1ph
|
|
Table 11 Low-Voltage, Three-Phase PDUs
|
|
Voltage
|
200 to 208 VAC 3ph
|
Frequency
|
50/60 Hz
|
Current
|
34.6A max. per phase
|
Power rating
|
25 kVA
|
Output current
|
120A (6 x 20A)
|
Outlets
|
42 x C13, 6 x C19
|
Outlet groups
|
6
|
Group protection (UL489 2-pole circuit breaker)
|
20A
|
Datacenter receptacle
|
IEC309 60A 4-pin 250VAC 3ph IP67
|
Number of inputs
|
2 x 60A 3ph
|
|
Table 12 High-Voltage, Single-Phase PDUs
|
|
Voltage
|
220 to 240 VAC
|
Frequency
|
50/60 Hz
|
Current
|
32A maximum per input
|
Power rating
|
22 kVA
|
Output current
|
96A (3 x 32A)
|
Outlets
|
42 x C13, 6 x C19
|
Outlet groups
|
6
|
Group protection (UL489 1-pole circuit breaker)
|
20A
|
Datacenter receptacle
|
IEC 60309 32A with 3-pin 250 VAC IP44
|
Number of inputs
|
3x32A 1ph
|
|
Table 13 High-Voltage, Three-Phase PDUs
|
|
Voltage
|
220/380 to 240/415 VAC 3ph
|
Frequency
|
50/60 Hz
|
Current
|
18A maximum per input
|
Power rating
|
25 kVA
|
Output current
|
109A (6 x 18.1A)
|
Outlets
|
42 x C13, 6 x C19
|
Outlet groups
|
6
|
Group protection (UL489 1-pole circuit breaker)
|
20A
|
Datacenter receptacle
|
IEC309 32A 5-pin 230/400V 3ph IP44
|
Number of inputs
|
2 x 25A 3ph
|
|