Power Cabling (Three Phase)

Depending on the configuration, some components might not be present. Slots U27 - U35 might contain a compute server, or storage servers, or nothing. See SuperCluster Rack Components.

From
Slot
From
Component
To
PDU-A
To
PDU-B
U41
(optional) Storage server 4
G5-4
G2-2
U39
(optional) Storage server 5
G5-3
G2-3
U37
(optional) Storage server 6
G4-6
G1-0
U35
(optional) Storage server 7
G5-1
G2-5
U33
(optional) Storage server 8
G5-0
G2-6
U31
(optional) Storage server 9
G4-4
G1-2
U29
(optional) Storage server 10
G4-3
G1-3
U27
(optional) Storage server 11
G3-4
G0-2
U27
(optional) Compute server:
AC0
AC2
AC4
G3-7
G4-7
G5-7
AC1
AC3
AC5
G0-7
G1-7
G2-7
U26
ZFS storage controller
G4-5
G1-1
U25
ZFS storage controller
G3-6
G0-0
U24
IP switch (leaf)
G2-6
G5-0
U20
ZFS disk shelf
G3-5
G0-1
U19
Ethernet management switch
G2-5
G5-1
U18
IB switch (leaf)
G2-4
G5-2
U8
Compute server:
AC0
AC2
AC4
G0-7
G1-7
G2-7
AC1
AC3
AC5
G3-7
G4-7
G5-7
U6
Storage server 3
G1-1
G4-5
U4
Storage server 2
G1-0
G4-6
U2
Storage server 1
G0-1
G3-5
U1
IB spine switch (if present)
G0-0
G3-6

Related Information