Go to main content

Oracle® SuperCluster M8 and SuperCluster M7 Installation Guide

Exit Print View

Updated: January 2019
 
 

PDU Thresholds (Single- and Dual-Server Models With 3 Storage Servers)

Table 18  22 kVA Single-Phase PDUs
Low Voltage
Low Voltage
High Voltage
High Voltage
PDU A
PDU B
Warning (Amps)
Alarm (Amps)
Warning (Amps)
Alarm (Amps)
M1-3
M1-1
3
4
3
4
M1-2
M1-2
18
23
17
21
M1-1
M1-3
29
36
26
32
Table 19  24 kVA 3-Phase PDUs
Low Voltage
Low Voltage
High Voltage
High Voltage
PDU A
PDU B
Warning (Amps)
Alarm (Amps)
Warning (Amps)
Alarm (Amps)
M2-3
M1-3
3
4
0
1
M2-2
M1-2
8
10
3
4
M2-1
M1-1
5
7
6
8
M1-3
M2-3
24
31
13
16
M1-2
M2-2
24
30
13
17
M1-1
M2-1
23
30
12
16