PDU Electrical Specifications
The following tables describe the PDU electrical specifications, including the
number and type of connectors and receptacles.
Table 3 Specifications for North and South America, Japan, and Taiwan Low-Voltage
Single Phase PDUs
|
|
|
|
Number of Inputs
|
2
|
3
|
3
|
Source Voltage
|
200-240V
|
200-240V
|
200-240V
|
Frequency
|
50/60 Hz
|
50/60 Hz
|
50/60 Hz
|
Max Line Current
|
24A
|
24A
|
36.8
|
Phase Current
|
N/A
|
N/A
|
N/A
|
Nominal Power Rating
|
10KVA
|
15KVA
|
22KVA
|
Recommended Circuit Breaker
|
30A
|
30A
|
50A
|
Outlets
|
42 x C13 6 x C19
|
42 x C13 6 x C19
|
42 x C13 6 x C19
|
Outlet Groups
|
6
|
6
|
6
|
Max Group Current
|
20A
|
20A
|
20A
|
Output Voltage
|
200-240V
|
200-240V
|
200-240V
|
Data Centre Receptacle
|
1ph 2W + ground 30A NEMA L6-30
|
1ph 2W + ground 30A NEMA L6-30
|
1ph 2W + ground 30A NEMA L6-30
|
|
Table 4 Specifications for North and South America, Japan, and Taiwan Low-Voltage
Three Phase PDUs
|
|
|
|
|
|
Number of Inputs
|
1
|
1
|
2
|
3
|
3
|
Source Voltage
|
200-220V
|
200-220V
|
200-220V
|
200-220V
|
200-220V
|
Frequency
|
50/60 Hz
|
50/60 Hz
|
50/60 Hz
|
50/60 Hz
|
50/60 Hz
|
Max Line Current
|
24A
|
40A
|
34.6A
|
24A
|
34.6A
|
Phase Current
|
13.85A
|
23A
|
20A
|
13.85A
|
20A
|
Nominal Power Rating
|
8.6KVA
|
15KVA
|
24KVA
|
26KVA
|
37KVA
|
Recommended Circuit Breaker
|
30A
|
50A
|
50A
|
30A
|
50A
|
Outlets
|
42 x C13 6 x C19
|
42 x C13 6 x C19
|
42 x C13 6 x C19
|
42 x C13 6 x C19
|
42 x C13 6 x C19
|
Outlet Groups
|
6
|
6
|
6
|
6
|
9
|
Max Group Current
|
14A
|
20A
|
20A
|
14A
|
20A
|
Output Voltage
|
200-240V
|
200-240V
|
200-240V
|
200-240V
|
200-240V
|
Data Centre Receptacle
|
3ph 3W + ground 30A IEC60309 NEMA L21-30P
|
3ph 3W + ground 60A IEC60309
|
3ph 3W + ground 60A IEC60309
|
3ph 3W + ground 30A IEC60309 NEMA L21-30P
|
3ph 3W + ground 60A IEC60309
|
|
Table 5 Specifications for EMEA and APAC High-Voltage Single Phase PDUs
|
|
|
Number of Inputs
|
2
|
3
|
Source Voltage
|
200-240V
|
200-240V
|
Frequency
|
50/60 Hz
|
50/60 Hz
|
Max Line Current
|
25A
|
32A
|
Phase Current
|
25A
|
32A
|
Nominal Power Rating
|
10KVA
|
15KVA
|
Recommended Circuit Breaker
|
30A
|
30A
|
Outlets
|
42 x C13 6 x C19
|
42 x C13 6 x C19
|
Outlet Groups
|
6
|
6
|
Max Group Current
|
20A
|
20A
|
Output Voltage
|
200-240V
|
200-240V
|
Data Centre Receptacle
|
1ph 2W + ground 32A IEC60309 3P 6H 230V
|
1ph 2W + ground 32A IEC60309 3P 6H 230V
|
|
Table 6 Specifications for EMEA and APAC High-Voltage Three Phase PDUs
|
|
|
|
|
|
Number of Inputs
|
1
|
1
|
2
|
3
|
3
|
Source Voltage
|
220/380 - 240/415VAC 3Ø
|
220/380 - 240/415VAC 3Ø
|
220/380 - 240/415VAC 3Ø
|
220/380 - 240/415VAC 3Ø
|
220/380 - 240/415VAC 3Ø
|
Frequency
|
50/60 Hz
|
50/60 Hz
|
50/60 Hz
|
50/60 Hz
|
50/60 Hz
|
Max Line Current
|
16A
|
21A
|
16A
|
16A
|
18A
|
Phase Current
|
16A
|
21A
|
16A
|
16A
|
18A
|
Nominal Power Rating
|
11KVA
|
15KVA
|
24KVA
|
33KVA
|
37KVA
|
Recommended Circuit Breaker
|
16/20A
|
25A
|
25A
|
16/20A
|
25A
|
Outlets
|
42 x C13 6 x C19
|
42 x C13 6 x C19
|
42 x C13 6 x C19
|
42 x C13 6 x C19
|
42 x C13 6 x C19
|
Outlet Groups
|
6
|
6
|
6
|
6
|
9
|
Max Group Current
|
20A
|
20A
|
18A
|
16A
|
18A
|
Output Voltage
|
220-240V
|
220-240V
|
220-240V
|
220-240V
|
220-240V
|
Data Centre Receptacle
|
3ph 4W + ground 16A IEC60309 5P 6h 400V
|
3ph 4W + ground 32A IEC60309 5P 6h 400V
|
3ph 4W + ground 32A IEC60309 5P 6h 400V
|
3ph 4W + ground 32A IEC60309 5P 6h 400V
|
3ph 4W + ground 32A IEC60309 5P 6h 400V
|
|