Oracle® Rack Cabinet 1242 Power Distribution Units User's Guide

Exit Print View

Updated: March 2018
 
 

Types of PDU Metering Unit SNMP Traps (Enhanced PDU)

The following table describes the SNMPv2 traps the metering unit can send to SNMP agents on the network (over UDP port 162). In the trap descriptions, InputNum/LineNum corresponds to the input number and line number of the PDU (for example, Input1/Line2).


Note -  The InputNum for SNMP Traps start at 1, not 0.
SNMP Trap
SNMP Notification
Description
Keep alive
KeepAlive-Trap
The PDU sends a KeepAlive-Trap message to the SNMP host to ensure that the link between them is operational.
Dead
Dead-Trap
Sent after a PDU power cycle.
Current Info
Info-Trap on InputNum/LineNum
Attached equipment is using less current than expected.
Current Warning
Warning-Trap on InputNum/LineNum
Attached equipment is using more current than expected.
Current Alarm
Alarm-Trap on InputNum/LineNum
Attached equipment is using a critical amount of current and requires immediate attention.
Current Out of balance
OutOfBalance-Trap on InputNum/LineNum
The equipment attached to one phase is using more current than the other phases on the input. The PDU and attached equipment require immediate attention.
Current Return to normal
ReturnToNormal-Trap on InputNum/LineNum
After sending an alarm trap, the attached equipment has returned to using the expected amount of current.
Voltage Warning
Warning-Trap on InputNum/LineNum
Attached equipment is operating with undesired but acceptable voltage level.
Voltage Alarm
Alarm-Trap on InputNum/LineNum
Attached equipment is operating with an unacceptable voltage level.
Voltage return to normal
ReturnToNormal-Trap on InputNum/LineNum
Attached equipment is operating with an expected voltage level.