Go to main content

Oracle® Rack Cabinet 1242 Power Distribution Units User's Guide

Exit Print View

Updated: March 2018
 
 

Relationship Between Modules and Outlet Groups Overview

The metering unit monitors modules, which are collections of PDU power outlet groups. Depending on the PDU, a module might contain all of the outlet groups on the PDU, or a subset of the groups. The metering unit monitors the current flowing through each module, not through each outlet group.

A metering unit module might also be divided into phases, which can either correspond to each power input lead in single-phase PDUs, or the separate phases in three-phase PDUs.

Single-Phase PDU Module and Outlet Group Relationship and Three-Phase PDU Module and Outlet Group Relationship show how the metering unit divides the outlet groups into modules and phases.

These topics also help you understand the metering unit's web interface, SNMP messages, system log messages, and LCD screen. For example, if your rack contains a high-voltage 37 kVA PDU and the PDU's LCD screen shows that phase 2 of module 3 is using excessive current, the equipment connected to outlet group 7 needs attention.


Note -  Refer to the labels on the PDUs to see the locations of these outlet groups.