Oracle® Rack Cabinet 1242 Power Distribution Units User's Guide

Exit Print View

Updated: March 2018
 
 

Three-Phase PDU Input and Outlet Group Relationship

Figure 5  Three-Phase PDU Input and Outlet Group Relationship

image:Figure showing the relationship between the metering unit inputs                             and the 3-phase PDU outlet groups.


Note -  For three-phase, low-voltage PDUs, each metering unit phase reports current from two outlet groups. Input phase 1 reports a combination of current from outlet groups 0 and 2 (3 and 5, or 6 and 8, depending on which input). Input phase 2 reports a combination of current from outlet groups 1 and 0 (4 and 3, or 7 and 6, depending on which input). Input phase 3 reports a combination of current from outlet groups 2 and 1 (5 and 4, or 8 and 7, depending on which input).
Table 14  Relationship Between Metering Unit Inputs and Outlet Groups on Three-Phase PDUs
PDU Type
Power Input
Lead Number
Input Phase
Outlet Group
15 kVA
0
Phase 1
0, 3
15 kVA
0
Phase 2
1, 4
15 kVA
0
Phase 3
2, 5
24 kVA
0
Phase 1
0
24 kVA
0
Phase 2
1
24 kVA
0
Phase 3
2
24 kVA
1
Phase 1
3
24 kVA
1
Phase 2
4
24 kVA
1
Phase 3
5