Install a DIMM

When servicing the components in this section, unplug the AC power cords and use ESD protection.

image:An illustration showing how to wear an anti static wrist strap.

Use this procedure to install a DIMM into a slot on a memory riser (MR) card.

Before You Begin

  1. Ensure that the DIMM ejector levers at both ends of the DIMM slot are in a fully open position.
  2. Align the DIMM with the empty slot.

    The DIMM is keyed with a notch that needs to align with a protrusion in the DIMM slot. The keying ensures that the DIMM is installed correctly.


    image:An illustration showing the DIMM aligned with the slot using the key.
  3. Gently and evenly push the DIMM into the slot until the ejector levers rise.

    The levers rise as the DIMM is pushed further into the slot.


    image:An illustration showing how to properly insert the DIMM into the slot.
  4. Ensure that the levers have risen completely and have locked the DIMM in the slot.
    image:An illustration showing the DIMM locked into place in its slot.
  5. Repeat the above steps until all replacement DIMMs are installed.

    Caution

    Caution  -  Component damage. Open DIMM ejector levers can break off during the installation of the memory riser (MR) card. All populated and unpopulated DIMM slot ejector levers on the MR card must be in the fully-closed position before installing the card in the server. Ensure that all levers are closed and locked.


Next Steps