HDDs are hot-swappable and can be removed and installed while the controller is running without affecting other hardware capabilities. Use the following procedure to replace a ZS7-2 HDD. For information on disk compatibility, see the Oracle Systems Handbook.
If you are not physically at the system, go to the Maintenance > Hardware section of the BUI, click the right-arrow icon for the controller, and note the ID of the faulted drive, which has an amber icon. To highlight the location of the drive in the controller picture, click on the drive ID. To view details about the faulted drive, click its information icon and then click Active Problems.
If you are physically at the system, the amber Service Action Required
indicator on the HDD should be lit. Additionally, you can click the locator
icon
in the BUI to flash the locator indicator on the
faulted drive.
The drive location in the following figure is for illustration purposes only.
|
![]() | Caution - The latch is not an ejector. Do not open the latch too far to the right. Doing so can damage the latch. |
The Oracle ZFS Storage Appliance software automatically detects and configures the new drive.