Installation Tools (Storage Array)

To install the storage array, you need the following tools:

  • Phillips head No. 2 screwdriver that is a minimum of 4 inches long.

  • A mechanical lift is highly recommended because the storage array can weigh approximately 110 lbs (50 kg). At least three people are required: two to install the storage array and one spotter to engage the rails. If a mechanical lift is not available, remove the power supply with fan modules to reduce the weight.

Use one of the following racks for the storage array:

  • Sun Rack II 1042/1242 cabinet 310

  • Any 19-inch wide, 4-post, EIA-compatible rack or cabinet with a front-to-back depth between vertical cabinet rails of 61 cm to 91 cm (24 in. to 32 in.). The cabinet must have either 9.5 mm square holes or 7 mm round holes. Cabinets must be able to support the weight of all equipment contained within them.

Position the rack where the storage array is to be installed adjacent to the rack where the controller is installed, if separate. Stabilize the cabinet and lock the casters. To facilitate access, remove doors from cabinets.