PDU Power Cord Specifications
Six AC PDU power cords deliver power to the server. Two types of PDU power cords
are available to support regional power source connections.
Note -
All six PDU power cords must be connected to the facility AC power receptacles
to power the server.
|
|
|
North America, Japan, and Taiwan
|
4m (13 ft, 1.5 in.)
|
30A, 120/208V, 3-phase, NEMA L21-30P
|
Europe, Middle East, Africa, and the rest of the world
|
4m (13 ft, 1.5 in.)
|
16/20A, 400V, IEC 60309 IP44 (516P6S)
|
|
Note -
While the PDU power cords are 4m (13.12 ft.) long, 1 to 1.5m (3.3 to 4.9 ft.)
of the cords will be routed within the rack cabinet. The facility AC power
receptacles must be within 2m (6.6 ft.) of the rack.
| Caution -
The installation site must have a local power disconnect (for example,
circuit breakers) between the power source and the power cords. You
will use this local disconnect to supply or remove AC power from the server. See
Circuit Breaker Capacity Requirements for
more information.
|
| Caution -
Ensure that you install the server near your power grid's electrical outlets,
and ensure that these outlets are easily accessible in case you must detach the
power cords in an emergency.
|
Note -
Electrical work and installations must comply with applicable local, state, or
national electrical codes. Your facility manager or a qualified electrician must
connect these power cords to the facility power grids.