PDU Specifications
The rackmounted servers ship with two redundant three-phase PDUs. To support the power requirements of all
geographical regions, the PDUs can be either low voltage or high voltage.
-
Low-voltage PDU – North America, Japan, and
Taiwan.
-
High-voltage PDU – Europe, Middle East, Africa, rest of the
world.
Table 1 Low-Voltage 3 Phase PDU Specifications
|
|
|
Power rating
|
26 kVA
|
Grounded neutral provided in input cords, but not connected in
PDU
|
Type of input
|
Three phase (4W+GND)
|
|
Number of inputs
|
Three inputs each with a 30A plugs per PDU, or six total
inputs/plugs for system
|
|
Source voltage
|
190V 220VAC (208V nominal phase to phase voltage) 50/60
Hz
|
|
Line current per phase
|
24A max. per phase
|
PDU rated at 26KVA phase voltage 208V
Nominal current equals 26000/208
|
Amps per PDU
|
125A
|
|
Number of groups of outlets
|
9
|
|
Outlets types
|
C13 and C19
|
Per group: five C13 and one C19.
Total per PDU: forty five C13 and nine C19
|
Data center receptacle
|
NEMA L21-30R
|
|
Usable PDU power cord length
|
2m (6.6 feet)
|
PDU power cords are 4m long (13 feet), but sections are used
for internal routing in the rack
|
|
Table 2 High-Voltage 3 Phase PDU Specifications
|
|
|
Power rating
|
33 kVA
|
|
Type of input
|
Three phase (4W+GND)
|
|
Number of inputs
|
Three inputs each with a 16A plug or six inputs/plugs for
system
|
|
Source voltage
|
220 - 240VAC (230V nominal line to neutral voltage), 50/60 Hz,
maximum
|
|
Line current per phase
|
16A max. per phase
|
|
Amps per PDU
|
144A
|
PDU rated at 33KVA phase
Line voltage: 220V
Nominal current equals 33000/220
|
Number of groups of outlets
|
9
|
|
Outlet types
|
C13 and C19
|
Per group: five C13 and one C19
Total per PDU: forty five C13 and nine C19.
|
Data center receptacle
|
IEC 60309 16/20A 200-240VAC
|
Hubbell C520R6S or equivalent.
|
Usable PDU power cord length
|
2m (6.6 feet)
|
PDU power cords are 4m long (13 feet), but sections are used
for internal routing in the rack
|
|