PDU Specifications

The rackmounted servers ship with two redundant three-phase PDUs. To support the power requirements of all geographical regions, the PDUs can be either low voltage or high voltage.

  • Low-voltage PDU – North America, Japan, and Taiwan.

  • High-voltage PDU – Europe, Middle East, Africa, rest of the world.

Table 1  Low-Voltage 3 Phase PDU Specifications
Low Voltage PDU Specification
Details
Comments
Power rating
26 kVA
Grounded neutral provided in input cords, but not connected in PDU
Type of input
Three phase (4W+GND)
Number of inputs
Three inputs each with a 30A plugs per PDU, or six total inputs/plugs for system
Source voltage
190V 220VAC (208V nominal phase to phase voltage) 50/60 Hz
Line current per phase
24A max. per phase
PDU rated at 26KVA phase voltage 208V
Nominal current equals 26000/208
Amps per PDU
125A
Number of groups of outlets
9
Outlets types
C13 and C19
Per group: five C13 and one C19.
Total per PDU: forty five C13 and nine C19
Data center receptacle
NEMA L21-30R
Usable PDU power cord length
2m (6.6 feet)
PDU power cords are 4m long (13 feet), but sections are used for internal routing in the rack
Table 2  High-Voltage 3 Phase PDU Specifications
High-Voltage PDU Specifications
Details
Comments
Power rating
33 kVA
Type of input
Three phase (4W+GND)
Number of inputs
Three inputs each with a 16A plug or six inputs/plugs for system
Source voltage
220 - 240VAC (230V nominal line to neutral voltage), 50/60 Hz, maximum
Line current per phase
16A max. per phase
Amps per PDU
144A
PDU rated at 33KVA phase
Line voltage: 220V
Nominal current equals 33000/220
Number of groups of outlets
9
Outlet types
C13 and C19
Per group: five C13 and one C19
Total per PDU: forty five C13 and nine C19.
Data center receptacle
IEC 60309 16/20A 200-240VAC
Hubbell C520R6S or equivalent.
Usable PDU power cord length
2m (6.6 feet)
PDU power cords are 4m long (13 feet), but sections are used for internal routing in the rack