Go to main content

SPARC M8 and SPARC M7 Servers Installation Guide

Exit Print View

Updated: September 2017
 
 

Power Cord-to-PDU Relationship (SPARC M8-8 and SPARC M7-8)

A rackmounted SPARC M8-8 or SPARC M7-8 server ships with one factory-installed server in a Sun Rack II 1242 rack. A Sun Rack II 1242 rack can contain up three stand-alone servers, so you can install up to two more stand-alone servers into the same rack. For the proper installation locations, see SPARC M8-8 and SPARC M7-8 Server Locations in an Oracle Rack.

When facing the rear of the rack, the stand-alone server power cord-to-PDU connections are as follows.

image:Figure showing the power cord to PDU relationship between the SPARC                             M8-8 or SPARC M7-8 server power supplies and the PDUs. Table 3  Third SPARC M8-8 or SPARC M7-8 Server Power Cord Connections (Top)
Power Supply No.
AC input No.
PDU Outlet Group
AC Power Grid No.
5
5
PDU B group 2
1
4
4
PDU A group 8
0
3
3
PDU B group 1
1
2
2
PDU A group 7
0
1
1
PDU B group 0
1
0
0
PDU A group 6
0
Table 4  Second SPARC M8-8 or SPARC M7-8 Server Power Cord Connections (Middle)
Power Supply No.
AC input No.
PDU Outlet Group
AC Power Grid No.
5
5
PDU B group 3
1
4
4
PDU A group 5
0
3
3
PDU B group 5
1
2
2
PDU A group 4
0
1
1
PDU B group 4
1
0
0
PDU A group 3
0
Table 5  Rackmounted SPARC M8-8 or SPARC M7-8 Server Power Cord Connections (Bottom)
Power Supply No.
AC input No.
PDU Outlet Group
AC Power Grid No.
5
5
PDU A group 2
0
4
4
PDU B group 8
1
3
3
PDU A group 1
0
2
2
PDU B group 7
1
1
1
PDU A group 0
0
0
0
PDU B group 6
1

Related Information