![]() | Caution - While the fan modules provide some cooling redundancy, if a fan module fails, replace it as soon as possible to maintain server availability. When you remove one of the fans in the rear row (fans 3, 4, or 5), you must replace it within 30 seconds to prevent overheating of the server. |
![]() | Caution - The fan module contains hazardous moving parts. Unless the power to the server is completely shut down, replacing the fan modules is the only service permitted in the fan compartment. |
A customer can perform this procedure while the server is running. See Component Service Categories for more information about hot-service procedures.
See Prevent ESD Damage.
The Service Action Required LEDs are located on the fan module as shown in Locate a Faulty Fan Module.
![]() | Caution - When removing a fan module, do not rock it back and forth. Rocking fan modules can damage the fan board connectors. |
![]() | Caution - When changing fan modules, note that only the fan modules can be removed or replaced. Do not service any other components in the fan compartment unless the server is shut down and the power cords are removed. |
See Install a Fan Module.