Verify that your installation site meets the following criteria for the Fabric Interconnect F1-4:
Power: 100-127 / 200-240 VAC 8.5 A at 100 volts or 4 A at 180 volts 50 - 60 Hz 750 W (maximum) with chassis fully loaded
Each power supply should be connected to a separate 15-20 A AC branch circuit. Do not exceed the maximum power cord length of 15 feet (4.57 m).
![]() | Caution - For the Oracle Fabric Interconnect F1-4 only, input power cords are used as the main AC power disconnect. As a result, the facility power socket outlet shall be installed near the equipment and shall be easily accessible. |
Environmental: Operating Temperature 5-35℃ Maximum Recommended Operating Temperature (Ambient) 35℃ Relative Humidity (non-condensing) 10-80% at 35℃ Operating Altitude 2000m (maximum)
Cooling: The front and back of the chassis must be free of any obstruction to the airflow (front-to-back)
![]() | Caution - Air vents must not be blocked and must have free access to the room ambient air for cooling. Installation of the equipment in a rack should be such that the amount of airflow required for safe operation of the equipment is not compromised. |
Select a location in the rack in which to install the Oracle Fabric Interconnect. The location must accept a chassis with the following dimensions, as shown in Verifying Rack Space:
Weight: 45 lbs. (20.5 Kg) in shipping configuration (no I/O Modules installed) 53 lbs. with I/O modules installed (the fully loaded weight might differ depending on the number and type of modules installed.)