Oracle Fabric Interconnect Hardware User's Guide

Exit Print View

Updated: July 2016
 
 

Fabric Interconnect F1-4 Site Criteria

Verify that your installation site meets the following criteria for the Fabric Interconnect F1-4:

  • Power: 100-127 / 200-240 VAC 8.5 A at 100 volts or 4 A at 180 volts 50 - 60 Hz 750 W (maximum) with chassis fully loaded

    Each power supply should be connected to a separate 15-20 A AC branch circuit. Do not exceed the maximum power cord length of 15 feet (4.57 m).


    Caution

    Caution  -  For the Oracle Fabric Interconnect F1-4 only, input power cords are used as the main AC power disconnect. As a result, the facility power socket outlet shall be installed near the equipment and shall be easily accessible.


  • Environmental: Operating Temperature 5-35℃ Maximum Recommended Operating Temperature (Ambient) 35℃ Relative Humidity (non-condensing) 10-80% at 35℃ Operating Altitude 2000m (maximum)

  • Cooling: The front and back of the chassis must be free of any obstruction to the airflow (front-to-back)


    Caution

    Caution  - Air vents must not be blocked and must have free access to the room ambient air for cooling. Installation of the equipment in a rack should be such that the amount of airflow required for safe operation of the equipment is not compromised.


  • Rack Type: 4-post EIA rack

  • Client Servers: InfiniBand interface required

Select a location in the rack in which to install the Oracle Fabric Interconnect. The location must accept a chassis with the following dimensions, as shown in Verifying Rack Space:

  • Height: 3 1/2 inches (8.9 cm)

  • Weight: 45 lbs. (20.5 Kg) in shipping configuration (no I/O Modules installed) 53 lbs. with I/O modules installed (the fully loaded weight might differ depending on the number and type of modules installed.)

  • Width: 17-13/16 inches (45.4 cm)

  • Depth: 28-1/4 inches (71.8 cm)

  • Service Clearance: 18 inches (45.7 cm) (front and rear)

Figure 2  Verifying Rack Space

image:Illustration shows F1-4 cabinet dimensions and service clearance space.