Go to main content

Sun Rack II Power Distribution Units User's Guide

Exit Print View

Updated: September 2020
 
 

Single-Phase PDU Module and Outlet Group Relationship

Figure 3  Single-Phase PDU Metering Unit Module and Outlet Group Relationship

image:Figure showing the relationship between metering unit modules and                             PDU outlet groups on single-phase PDUs.

Table 11  Relationship Between Metering Unit Modules and Outlet Groups on Single-Phase PDUs
PDU Type
Metering Unit Module
Metering Unit Phase
Outlet Group
Power Input Lead Number
5 kVA
M1
Phase 1
0, 1, 2, 3, 4, 5
0
10 kVA
M1
Phase 1
0, 1, 2
0
Phase 2
3, 4, 5
1
15 kVA, 22kVA
M1
Phase 1
0, 1
0
Phase 2
2, 3
1
Phase 3
4, 5
2