Sun Rack II Power Distribution Units User's Guide

Exit Print View

Updated: September 2020
 
 

Input Parameters

Table 21  Input Parameters (get Command) Available Starting with FW 2.01
Parameters
Syntax
Response
pwr_input_power
pducli -> get pwr_input_power.x
pducli-> pwr_input_power.x=yyyyW
pwr_input_energy
pducli -> get pwr_input_energy.x
pducli-> pwr_input_energy.x=yyyyWh
pwr_input_max_load
pducli -> get pwr_input_max_load.x
pducli-> pwr_input_max_load.x=yyyyVA
pwr_input_load
pducli -> get pwr_input_load.x
pducli-> pwr_input_load.x=yyy%

Note -  Replace x with the input number (0 to 5).
Table 22  Input Parameters (get Command) Available Starting with FW 2.02
Parameters
Syntax
Response
pwr_input_outofbalance
pducli -> get pwr_input_outofbalance.x
(x=input number)
pducli-> pwr_input_outofbalance.x=yyya
(yyy=OutOfBalance Current in [A] for input x)
pwr_input_outofbalance_ threshold_alarm
pducli -> get pwr_input_outofbalance_threshold_alarm.x
(x=input number)
pducli-> pwr_input_outofbalance_threshold_alarm.x=yyya
(yyy=OutOfBalance-AlarmThreshold in [A] for input x)
pwr_input_outofbalance_ trap_enable
pducli -> get pwr_input_outofblance_trap_enable.x
(x=input number)
pducli-> pwr_input_outofbalance_trap_enable.x=On
(Or Off for input x)
Table 23  Inputs Parameters (set Command) Available Starting with FW 2.02
Parameters
Syntax
Response
power_input_energy
pducli -> set power_input_energy.x=0
(Only 0 allowed for clear energy)
pducli-> set OK (or an error message)
pwr_input_outofbalance_ threshold_alarm
pducli -> set pwr_input_outofbalance_threshold_alarm.x=yyy
(yyy=OutOfBalance-alarmThreshold in [A] for input x)
pducli-> set OK (or an error message)
pwr_input_outofbalance_trap_ enable
pducli -> set pwr_input_outofbalance_trap_enable.x=On
(Or Off for input x)
pducli-> set OK (or an error message)