Oracle® Rack Universal Power Distribution Unit User's Guide

Exit Print View

Updated: May 2019
 
 

Configuring SNMP Settings

  1. Select Device Settings → Network Services → SNMP.
  2. Enable or disable SNMP v1 / v2c or SNMP v3 by clicking a check box.

    The SNMP v1/v2c read-only access is enabled by default. The default Read Community String is public.

  3. To enable read-write access, type the Write Community String, where usually the string is private.
  4. If needed, type the MIB-II system group information.
    • sysContact – Contact person who manages system

    • sysName – Name assigned to the system

    • sysLocation – Location of the system

  5. Configure SNMP notifications.
    1. Select Enable SNMP Notifications.
    2. Select a notification type: SNMPv2c trap, SNMPv2c inform, SNMPv3 trap, and SNMPv3 inform.
    3. Specify the Notification type, Timeout, and Number of Retries.

      Note -  When you change any SNMP Notifications settings on the SNMP page, the settings in the System SNMP Notification Action are updated. To add more than three SNMP destinations, you can create new SNMP notification actions.
    4. For each SNMP destination, enter the Host, Port, and Community.
  6. To download the SNMP MIB for the HPDU to use with the SNMP manager, click the Download MIBs down arrow, and click the PDU2-MIB download link.

    Note -  If the built-in system SNMP Notification Rule is enabled and the SNMP destination is not set yet, you might need to configure the SNMP destination(s).
  7. Click Save.