Oracle® Rack Universal Power Distribution Unit User's Guide

Exit Print View

Updated: May 2019
 
 

Show the Inlet Pole Sensor Threshold Information

  1. To show the specified inlet pole sensor threshold information, type show sensor inletpole <n> <p> <sensor type>, and press Enter.
    • <n> is the number of the inlet whose pole sensors you want to query. For a single-inlet HPDU, <n> is always 1.

    • <p> is the label of the inlet pole whose sensors you want to query.

    Pole
    Label
    <p>
    Current Sensor
    Voltage Sensor
    1
    L1
    L1
    L1 - L2
    2
    L2
    L2
    L2 - L3
    3
    L3
    L3
    L3 - L1

    <sensor type> is one of the following inlet pole sensor types:

    Sensor Type
    Description
    current
    Current sensor
    voltage
    Voltage sensor
    activePower
    Active power sensor
    apparentPower
    Apparent power sensor
    powerFactor
    Power factor sensor
    activeEnergy
    Active energy sensor
    • Without the parameter "details," only the reading, state, threshold, deassertion hysteresis and assertion timeout settings of the specified inlet pole sensor are displayed.

    • With the parameter "details," more sensor information is displayed, including resolution and range.

    • If the requested sensor type is not supported, the "Sensor is not available" message is displayed.

  2. To show detailed information, type show sensor inletpole <n> <p> <sensor type> details, and press Enter.