Sending a Sensor Report

You can set the HPDU so that it automatically reports the latest readings or states of one or more sensors by sending a message or email or recording the report in a log. The sensor report can contain the following information.

  • Inlet sensors, including RMS current, RMS voltage, active power, apparent power, power factor and active energy.

  • Overcurrent protector sensors, including RMS current and tripping state.

  1. Select Device Settings → Event Rules → + New Action.
  2. For Action, select Send sensor report.
  3. In the Destination Actions section, select the method(s) to report sensor readings or states. The number of available methods varies, depending on how many messaging actions have been created.

    The messaging action types include:

    • Log event message

    • Syslog message

    • Send email

    • Send SMS message

  4. If no messaging actions are available, create them now.
  5. To select a method, select each one in the Available field, or to add all available methods, click Select All.
  6. To delete any method, click the X for a method in the Selected field, or to delete all methods, click Deselect All.
  7. In the Available Sensors list, select a sensor for the target:
    1. Click the first Up or Down arrow (far left) and select a target component.
    2. Click the second Up or Down arrow (middle) and select the sensor for the target.

      For example, to monitor the current reading of the Inlet 1, select Inlet 1 from the left field, and select RMS Current from the right field.

    3. To report additional sensors simultaneously, repeat the Step 7b to add more sensors.
    4. Click + to add the selected sensor to the Report Sensors list.
  8. To remove any sensor from the Report Sensors list:
    1. Select the sensor and click the - (Minus button).
    2. To select multiple sensors, press Ctrl+click or Shift+click to highlight the sensors.
  9. To send the sensor report, click Send Report Now.