Go to main content

Oracle® Rack Universal Power Distribution Unit User's Guide

Exit Print View

Updated: May 2019
 
 

Performing a Bulk Configuration

  1. On the source device, ensure the wanted profile is selected as the default. If not, start from Step 2. If yes, go to Step 3.
  2. (Optional) Select the desired bulk configuration profile.
    1. Log in to the source HPDU, whose settings you want to copy.
    2. Select Maintenance → Bulk Configuration.
    3. Click the row of the wanted profile to open the Edit Bulk Profile page.
    4. For the Default Profile option, click Select.
    5. Click Save.
  3. Save a bulk configuration file.
    1. Verify that you have the Administrator Privileges or Unrestricted View Privileges to download the configuration.
    2. Log in to the source HPDU if you did not log in yet.
    3. Select Maintenance → Bulk Configuration.
    4. If the selected Bulk Format value (see the following table) does not match your need, you can change it.
      Bulk Format Value
      Description
      Encrypted
      • Partial content is base64 encoded.

      • Its content is encrypted using the AES-128 encryption algorithm.

      • File is saved to the TXT format

      Cleartext
      • Content is displayed in clear text.

      • File is saved to the TXT format.

    5. Change any bulk configuration settings.
    6. Click Download Bulk Configuration.
    7. When prompted to open or save the configuration file, click Save.
  4. Perform a bulk configuration.
    1. Verify that you have the Administrator Privileges to upload the configuration.
    2. Log in to the target HPDU, which is the same model and runs the same firmware as the source HPDU.
    3. Select Maintenance → Bulk Configuration.
    4. Click Browse and select the configuration file.
    5. Click Upload & Restore Bulk Configuration to copy it.
    6. When prompted, type the admin password, and click Restore.
    7. Wait until the HPDU device resets and the login page re-appears.