Show the Inlet Sensor Threshold Information

  1. To show the specified inlet sensor threshold information, type show sensor inlet <n> <sensor type>, and press Enter.
    • <n> is the number of the inlet whose sensors you want to query. For a single-inlet HPDU, <n> is always 1.

    • <sensor type> is one of the following inlet sensor types:

    Sensor Type
    Description
    current
    Current sensor
    voltage
    Voltage sensor
    activePower
    Active power sensor
    apparentPower
    Apparent power sensor
    powerFactor
    Power factor sensor
    activeEnergy
    Active energy sensor
    unbalancedCurrent
    Unbalanced load sensor
    lineFrequency
    Line frequency sensor
    • Without the parameter "details," only the reading, state, threshold, deassertion hysteresis and assertion timeout settings of the specified inlet sensor are displayed.

    • With the parameter "details," more sensor information is displayed, including resolution and range.

    • If the requested sensor type is not supported, the "Sensor is not available" message is displayed.

  2. To show detailed information, type show sensor inlet <n> <sensor type> details, and press Enter.