Go to main content

Oracle® Rack Universal Power Distribution Unit User's Guide

Exit Print View

Updated: May 2019
 
 

Firmware Update through SCP

A firmware update through SCP is the same as any HPDU firmware update, where all user management operations are suspended and all login attempts fail during the SCP firmware update.

  1. Type scp <firmware file> <user name>@<device ip>:/fwupdate and press Enter.

    <firmware file> –- HPDU firmware file name. If the firmware file is not in the current directory, include the path in the file name.

    <user name> – Admin or any user profile with the Firmware Update permission.

    <device ip> – IP address of the HPDU that you want to update.

    SCP example – scp pdu-px2-030000-41270.bin admin@192.168.87.50:/fwupdate

    Windows PSCP example – pscp <firmware file> <user name>@<device ip>:/fwupdate

  2. When prompted, type the password, and press Enter.

    The system transmits the specified firmware file to the HPDU, and shows the transmission speed and percentage. When the transmission is complete, a message appears indicating that the HPDU starts the firmware update. The connection is closed.

  3. Wait until the upgrade finishes.