You must determine which power supply is faulty before you replace it.
See Chassis Status LEDs.
See Power Supply LEDs.
Start at Remove the Air Duct Assembly.
See Accessing the SP.
-> show /System/Open_Problems Open Problems (1) Date/Time Subsystems Component ------------------------ ------------------ ------------ Thu Dec 17 05:17:11 2015 Power PSx (Power Supply 1) fault.chassis.device.psu.fail (Probability:100, UUID:b516a939-23c2-ee8b-e997-d915ca03d044, Resource:/SYS/PSx, Part Number:7065505-01, Serial Number:C92517, Reference Document:http://support.oracle.com/msg/---) ->
where x is 0 or 1.
Start at Remove the Air Duct Assembly.
See Open Problem Faults and Oracle ILOM Legacy Target Replaceable Components.
-> show /System/power -t health Target | Property | Value ---------------------------------------------+------------+------ /System/Power | health | OK /System/Power/Power_Supplies/Power_Supply_0 | health | OK /System/Power/Power_Supplies/Power_Supply_1 | health | Service Required ->
If any power supply's health has a value other than OK, replace that power supply. Start at Remove the Air Duct Assembly.
-> show /SYS -t fault_state Target | Property | Value -------------------+-----------------------+------- /SYS | fault_state | OK . . . /SYS/PS0 | fault_state | OK /SYS/PS1 | fault_state | Faulted /SYS/SP | fault_state | OK ->
In the output, look for the rows beginning with /SYS/PS.
If any power supply's fault state has a value other than ok, replace that power supply. Start at Remove the Air Duct Assembly.