Oracle® InfiniBand Switch IS2-46 Service Manual

Exit Print View

Updated: September 2016
 
 

Determine if the Battery Is Faulty

You must determine if the battery is faulty before you replace it.

  1. Access the Oracle ILOM CLI.

    See Accessing the SP.

  2. Determine if the battery has become problematic.
    -> show /System/Open_Problems
    Open Problems (1)
    Date/Time                 Subsystems          Component
    ------------------------  ------------------  ------------
    Thu Dec 17 05:00:01 2015  System              MB (Motherboard)
     fault.chassis.battery.fail (Probability:100, UUID:76a2179a-51bd-c836-a7f1-af62953577fa, Resource:/SYS/MB, Part
     Number:7092577, Serial Number:AK00329231, Reference Document:http://support.oracle.com/msg/---)
    ->
  3. Determine if the battery has faulted.
    -> show /SYS/MB/V_VBAT alarm_status
     /SYS/MB/V_VBAT
     	Properties:
     		alarm_status = state_asserted
    ->

    If the alarm status is anything other than cleared, replace the battery. Start at Remove the Air Duct Assembly.

  4. If you are unable to determine if the battery is faulty, seek further information.

    See Detecting and Managing Faults.