Install a Fan Module
This procedure describes how to install a replacement fan module in the server.
Before You Begin
-
If you are installing a replacement fan module for one that has failed, check the indicator of
the failed fan slot to ensure the fault indicator is no longer lit.
This is necessary to ensure the indicator status is cleared before you insert the new fan. See
Fan Module Reference for fan module indicator
locations.
-
Orient the fan module so the connector on the bottom of the module is aligned with the
connector on the inside of the slot and all keying and labeling are correctly positioned.
The fan modules are keyed to ensure that they are installed in the correct orientation.
-
Slide the fan module into the slot until is stops.
-
Press downward on the top of the fan module at the Press Here to Latch label until the fan
module is fully seated.
-
Verify that the green OK indicator is lit.
-
Verify that the Top Fan indicator and the Service Action Required indicator on the server
front panel are not lit.
See Server Front Panel Features and Server Back Panel Features for locations of system
indicators.
-
If necessary, return the server to the normal rack position.
-
Ensure the cables are free from binding and pinching.
-
Slide the server into the rack until it locks into place.
-
If you performed a cold-service procedure, power on the server.